Datasheet

www.murata-ps.com/support
PRELIMINARY
ABSOLUTE MAXIMUM RATINGS
Conditions
Minimum Typical/Nominal Maximum Units
Input Voltage, Continuous 080Vdc
Input Voltage, Transient 100 mS max. duration 100 Vdc
Isolation Voltage Input to output 2250 Vdc
On/Off Remote Control Power on, referred to -Vin 0 13.5 Vdc
Output Power 0 200 W
Output Current Current-limited, no damage, short-circuit protected 0 60 A
Storage Temperature Range Vin = Zero (no power) -55 125 °C
Absolute maximums are stress ratings. Exposure of devices to greater than any of these conditions may adversely affect long-term reliability. Proper operation under conditions other than those
listed in the Performance/Functional Specifi cations Table is not implied nor recommended.
INPUT
Operating voltage range (V2) 364875Vdc
Start-up threshold (Default, confi gurable via PMBus) 33 34 35 Vdc
Undervoltage shutdown (Default, confi gurable via PMBus) 31 32 34 Vdc
Overvoltage shutdown (Default, confi gurable via PMBus) NA NA NA Vdc
Overvoltage Recover (Default, confi gurable via PMBus) NA NA NA Vdc
Internal Filter Type Pi
External Input fuse 20A
Input current
Full Load Conditions Vin = nominal 4.43 4.48 A
Low Line input current Vin = minimum 5.79 5.97 A
Inrush Transient Vin = 48V. TBD TBD A
2
-Sec.
Short Circuit input current 0.05 0.1 A
No Load input current Iout = minimum, unit=ON 50 100 mA
Shut-Down input currrent(Off, UV, OT) TBD TBD mA
Back Ripple Current TBD TBD mAp-p
GENERAL and SAFETY
Effi ciency Vin=48V, full load (V2) 92 93.2 %
Isolation Voltage
Input to output 2250 Vdc
Input to Baseplate 1500 Vdc
Output to Baseplate 1500 Vdc
Insulation Safety Rating functional
Isolation Resistance 10 M
Isolation Capacitance 1000 pF
Safety
Certifi ed to UL-60950-1, CSA-C22.2 No.60950-1, IEC/
EN60950-1, 2nd edition
Yes
Calculated MTBF
Per Telcordia SR-332, Issue 2, Method 1, Class 1, Ground Fixed,
Tcase=+25°C
1800 Hours x 10
3
DYNAMIC CHARACTERISTICS
Switching Frequency (Confi gurable via PMBus)
Fixed Frequency Control

150
KHz
Variable Frequency Control (Default)

NA
KHz
Turn On Time (Default, Confi gurable via PMBus)
Vin On to Vout Regulated

45 mS
Remote On to Vout Regulated

25 mS
Vout Rise Time (Default, Confi gurable via PMBus)
From 0%~100%

20
mS
Vout Fall Time of Regulated Off (Default, Confi gurable via PMBus)
From 100%~0%

13
mS
Dynamic Load Response 50-75-50%, 1A/us,within 1% of Vout
TBD TBD µSec
Dynamic Load Peak Deviation same as above
TBD TBD mV
DBQ0360V2: 3.3V/60A FUNCTIONAL SPECIFICATIONS (VOLTAGE APPLIED TO SCL SDA SMBALERT AND ON/OFF 2, MIN: -0.3V MAX: 3.6V)
DBQ/DVQ Series
420W Digital Fully Regulated Intermediate
DC-DC Bus Converter
MDC_DBQ Series.B02Δ Page 3 of 31