Datasheet

On/Off Control
The input-side, remote On/Off Control function (pin 3) can be ordered to operate 
with either polarity. Positive-polarity devices ("C" suffix) are enabled when pin 
3 is left open (or is pulled high, +13V to VIN applied with respect to –Input, pin 
2, see Figure 2). Positive-polarity devices are disabled when pin 3 is pulled low 
(0-0.8V with respect to –Input). Negative-polarity devices are off when pin 3 is 
left open (or pulled high, 3.5V to VIN), and on when pin 3 is pulled low (0-0.5V). 
See Figure 5.
Dynamic control of the remote on/off function is best accomplished with a 
mechanical relay or an open-collector/open-drain drive circuit (optically isolated 
if appropriate). The drive circuit should be able to sink appropriate current (see 
Performance Specs) when activated and withstand appropriate voltage when 
deactivated.
Applying an external voltage to pin 3 when no input power is applied to the 
converter can cause permanent damage to the converter. 
3
2
1
+INPUT
13V CIRCUIT
5V CIRCUIT
–INPUT
ON/OFF
CONTROL
Figure 4. Driving the Positive Polarity On/Off Control Pin
Figure 5. Driving the Negative Polarity On/Off Control Pin
Start-Up Time
The VIN to VOUT start-up time is the interval of time where the input voltage crosses 
the turn-on threshold point, and the fully loaded output voltage enters and remains 
within its specified accuracy band. Actual measured times will vary with external 
output capacitance and load. The BWR 15-17W Series implements a soft start 
circuit that limits the duty cycle of the PWM controller at power up, thereby limiting 
the Input Inrush current. 
The On/Off Control to VOUT start-up time assumes the converter has its nominal 
input voltage applied but is turned off via the On/Off Control pin. The specification 
defines the interval between the time at which the converter is turned on and the 
fully loaded output voltage enters and remains within its specified accuracy band. 
Similar to the VIN to VOUT start-up, the On/Off Control to VOUT start-up time is also 
governed by the internal soft start circuitry and external load capacitance. 
If loading from +/– Outputs to Output Return is symmetrical, the voltage at 
Output pins with respect to Output Return will also be symmetrical. An unbal-
ance in loading will consequently result in a degraded VOUT regulation accuracy 
from +/– Outputs to Output Return ( –Output to +Output regulation will still be 
within specification) with a load step from minimum to maximum load and with 
the other output at full load, the maximum deviation is 2.5% VOUT nominal.
3
2
1
+INPUT
–INPUT
ON/OFF
CONTROL
15.5
15.4
15.3
15.2
15.1
15
14.9
14.8
14.7
BWR-15/575-D48A Unbalanced Output Load Regulation
Output Load Regulation (%)
+/–15VOUT
  0 10 20 30 40 50 60 70 80 90 100
+15V @ 0A to 0.575A
–15V @ 0.575A
–15V @ 0A to 0.575A
+15V @ 0.575A
Current Limiting 
When output current increases to approximately 15% to 50% above the rated 
output current, the DC/DC converter will go into a current limiting mode. In 
this condition the output voltage will decrease proportionately with increases 
in output current, thereby maintaining a somewhat constant power dissipa-
tion. This is commonly referred to as power limiting. Current limit inception 
is defined as the point where the full-power output voltage falls below the 
specified tolerance. See Performance/Functional Specifications. If the load 
current being drawn from the converter is significant enough, the unit will go 
into a short circuit condition. See "Short Circuit Condition." 
Short Circuit Condition
When a converter is in current limit mode the output voltages will drop as 
the output current demand increases. If the output voltage drops too low, the 
magnetically coupled voltage used to develop primary side voltages will also 
drop, thereby shutting down the PWM controller. 
Following a time-out period, the PWM will restart, causing the output voltages 
to begin ramping to their appropriate values. If the short-circuit condition 
persists, another shutdown cycle will be initiated. This on/off cycling is 
referred to as "hiccup" mode. The hiccup cycling reduces the average output 
current, thereby preventing internal temperatures from rising to excessive 
levels. The BWR 15-17W Series is capable of enduring an indefinite short 
circuit output condition. 
Thermal Shutdown
These BWR converters are equipped with Thermal Shutdown Circuitry. If 
environmental conditions cause the internal temperature of the DC/DC con-
verter rises above the designed operating temperature, a precision tempera-
ture sensor will power down the unit. When the internal temperature decreases 
below the threshold of the temperature sensor the unit will self start.
Figure 4. Output Voltage Accuracy vs. Imbalanced Loading
BWR Series
15-17W, Dual Output DC/DC Converters
MDC_BWR15-17W.D01  Page 5 of 9
www.murata-ps.com/support









