EN Installation Manual Air Conditioner DC Duct Type Modelos: MUCR 12 HF2 MUCR 18 HF2 MUCR 24 HF2 MUCR 30 HF2 MUCR 36 HF2 MUCR 48 HF2 MUCR 60 HF2 For correct installation, read this manual before starting installation. This manual may be subject to change without notice for purpose of improvement..
Air Conditioner DC Duct Type EN ÍNDICE 1. INSTALLATION INFORMATION..............................................................................................................2 2. ACCESORIES.........................................................................................................................................2 3. CAUTIONS ON REMOTE CONTROLLER INSTALLATION....................................................................2 4. INSTALATION PLACE............................................
Air Conditioner DC Duct Type EN 1. INSTALLATION INFORMATION • To install properly, please read this manual at first. The air conditioner must be installed by qualified persons. • When installing the indoor unit or its tubing, please follow this manual as strictly as possible. • When all the installation work is finished, please turn on the power only after a thorough check. • No further announcement if there is any change of this manual caused by product improvement.
Air Conditioner DC Duct Type EN NOTES BEFORE INSTALLATION 1. Select the correct carry-in path. 2. Move this unit as originally packaged as possible. 3. If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances 4. INSTALLATION PLACE The Indoor Unit • There is enough roomfor installation and maintenance. • The ceiling is horizontal, and its structure can endure the weight of the indoor unit.
Air Conditioner DC Duct Type EN THE INSTALLATION OF HANGING SCREW BOLTS 5. INDOOR UNIT INSTALLATION Install the main body Installing Ø10 hanging screw bolts. (4 bolts) Please refer to the following figure for the distance measurement between the screw bolts. Please install with Ø10 hanging screw bolts. The handling to the ceiling varies fromthe constructions, consult the construction personnels for the specific procedures.
Air Conditioner DC Duct Type EN 6.
Air Conditioner DC Duct Type EN Dimensions A D E F G H 920 210 635 570 65 713 35 119 1140 210 635 570 65 933 35 119 1035 200 80 1180 350 920 270 635 570 65 713 35 179 815 260 20 30~36 1140 270 775 710 65 933 35 179 1035 260 20 1180 490 48~60 1200 300 865 800 80 968 40 204 1094 288 45 1240 500 12~18 24 B C Size of mounted lug Air returning Air Outlet I J K 815 200 80 L 960 350 960 350 7. ADJUST AIRVENTILATED DIRECTION 1.
Air Conditioner DC Duct Type EN 8. INSTALL THE CONNECTING PIPE CAUTION Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements: 30 MUCR-HF 12 18 24 1F Outdoor Unit Top 5 12 12 15 MAX . HEIGHT Outdoor Unit Bottom 5 9 9 9 Max. length 10 25 25 25 30 3F 20 12 30 36 1F 20 12 30 36 3F 20 12 30 48 1F 25 20 50 48 3F 30 20 50 NOTICE FOR BENDABLE PIPE • The bending angle should not exceed 90 .
Air Conditioner DC Duct Type EN 9. REFRIGERANT PIPE CONNECTION Flaring Chart 19 The necessary filling amount of refrigerant Refrigerant volume to be added is calculated according to outdoor unit installation manual . Be sure to add refrigerant measuring by a scale. L: The length of the pipe Please record the quantity added and store it carefully for future maintenance. Chart 20 1. Cut a pipe with a pipe cutter. 2. Insert a flare nut into a pipe and flare the pipe.
Air Conditioner DC Duct Type EN 11. WIRING Check the leakage Check all the joints with the leak detector or soap water. Attaching wiring 1. The air conditioner should use separate power supply with rated voltage 2. The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit. 3. The wiring work should be done by qualified persons according to circuit drawing. 4.
Air Conditioner DC Duct Type EN 12.
Air Conditioner DC Duct Type EN 12. WIRING CHART INDOOR UNIT Power Supply1-Phase 220-240V (3-core cable 3x1.0mm²) 3-core shielded cable to CCM (3x0.5mm²) OUTDOOR UNIT 3-core shielded cable (3 x 0.5 mm²) Power Supply1-Phase 220-240V (3-core cable 3x4 mm²) Models 18-60 (with 1-Phase outdoor unit) INDOOR UNIT 3-core shielded cable to CCM (3x0.5mm²) Power Supply1-Phase 220-240V (3-core cable 3x1.0mm²) OUTDOOR UNIT 3-core shielded cable (3 x 0.5 mm²) Power Supply1-Phase 220-240V (5-core cable 5x2.
Air Conditioner DC Duct Type EN The Specification of Power Type Power Phase Frequency and volt Circuit breaker / Fuse (A) Indoor unit power wiring(mm2) Indoor/Outdoor connecting wiring 2 (mm ) 18000 Btu/h 24000 Btu/h 36000-60000 Btu/h 1-Phase 1-Phase 3-Phase 220-240V - 50 Hz 220-240V - 50 Hz 380-415V - 50 Hz 30/25 40/25 40/25 3 x 1,0 3 x 1.
Air Conditioner DC Duct Type EN CAUTION 1.The system together have 64units (0-63),everyone has only system addresscode, If two addresses are the same in one system, the abnormal operation will occur. 2.Please switch off the power before setting,otherwise the unexpected error will occur. Código interruptor de palanca Capacidad (Btu/h) 4 5 18000 24000 8 36000 9 9 48000 60000 13. NETWORK ADDRESS SET Every air-conditioner in network has only one network address to distinguish each other.
Air Conditioner DC Duct Type EN 14. TEST OPERATION 2) The outdoor unit a. Whether there is vibration or abnormal noise during operation. b. Whether the generated wind, noise, or condensed water by the air conditioner have influenced your neighborhood. c. Whether any of the refrigerant is leaked. 1.The test operation must be carried out after the entire installation has been completed. 2. Please confirm the following points before the test operation: 3.
Air Conditioner DC Duct Type EN 17.