Create an exit point for the wires from the call point to the external switch by
removing the section indicated in the illustration below with a pair of pliers.
Break away case here to
create exit point for wires.
A pre-wired header is provided with the call point and this should be attached
paying particular attention to forming the wires as shown below to avoid
snagging them when sliding the unit on to the back plate.
The header is wired as follows:
Pin 1 = External alarm activate.
Pin 2 = Ground (for both contacts).
Pin 3 = External alarm cancel. Connecting this input to the ground pin has the
same effect as a long press on the front button of the call point, clearing
any alarm that the call point has raised.
Place wires as shown