Installation Instructions

Table Of Contents
EkoTek System Installation and Configuration Manual Browser Interface
Alarm clearance: Alert text:
Modifiable text appears in the message sent to Pagers when any alarm for this device is
cleared. Defaults to ‘Cleared’.
Alarm escalation period:
If an active alarm is not cleared within this period of time, then the device re-sends the
alarm with a raised escalation level (minutes).
Submit:
Submit the requested configuration.
Repeater Details
The device mode entry page hardware type, followed by the modifiable device mode name
(defaults 1->32).
Upstream channel/Downstream channel:
(Repeater only) Used to determine the RF channel of the Repeater, selected via drop
down menu (1 -> 16) and As parent Allows a Repeater to use the same RF channel as its
parent device. The default mode of operation, this allows for a self-organising radio
network.
Location range:
Defines the range of the location signal from the Repeater. The default value is ‘2’ which
gives an approximate range in indoor environments of 3m. A value of ‘1’ gives the shortest
range and ‘10’ the longest range. The range should not be set to high values in
deployments where location signal penetration through walls and floors is not desired.
Submit:
Submit the requested configuration.