Specifications
8. M560 SPECIFICATIONS
INPUT
Rated Un Direct connected voltages between 57.8
and 600V. Specify nominal.
Range 2-120% Un
Burden 0.5VA per phase
Overload 1.5 x Un continuous
4 x Un for 1 second
Rated In 1 or 5 amp
Range 0-120%
Burden 0.5VA per phase
Overload 4 x In continuous
50 x In for 1 second
Frequency 50 / 60 Hz nominal range
45/65Hz
59
SYSTEMS M560-AT1 Single phase
M560-AT1-3 Single phase 3 wire
M560-AT4 3 phase 3 wire unbalanced load
M560-AT9 3 phase 4 wire unbalanced load
ACCURACY
Specified@ 23 °C 10%-Un 10%-In
Parameters unless stated Class 0.3% to IEC 688
Volts and Amps Class 0.25% to IEC 688
Frequency Class 0.1Hz to IEC 688
Power Factor Class 1.0% to IEC 688
Active & Reactive Energy 1% of reading IEC 1036
APPLIED STANDARDS
General IEC 688 BSEN60688, BS4889, IEC 359
EMC Emissions EN61326-1
Immunity EN61326-2
Safety EN61010-1