Specifications
6.5 Voltage Transformers
Connection of voltages higher than the rated voltage, that
is specified on the M560 data label, is possible using
external voltage transformers. These
transformers must be at least Class 1 accuracy. The
secondary of these transformers must have the same
nominal voltage as that specified on the data label on the
side of the M560. e.g. If the M560 had a voltage specified
as 110 Volts Line to Line, then a Transformer with Ratio of
6600/110 volt can be used, once this ratio has been
programmed into the M560 (See section 4.21.) But if the
ratio was 6600/400V the unit would have to be returned to
the factory or distributor to have internal component
changes to cater for the 400 Volt input.