5.5 Voltage Transformers
Connection of voltages higher than the rated voltage, that
is specified on the M550 data label, is possible using
external voltage transformers. These
transformers must be at least Class 1 accuracy. The
secondary of these transformers must have the same
nominal voltage as that specified on the data label on the
side of the M550. e.g. If the M550 has a voltage specified as
110 Volts Line to Line, then a Transformer with Ratio of
6600/110 volt can be used, once this ratio has been pro-
grammed into the M550 (See section 4.21.) But if the ratio
was 6600/400V the unit would have to be returned to the
factory or distributor to have internal component changes
to cater for the 400 Volt input.