Specifications

45
3) The number of parity errors detected by the node.(counts
up to 255 then flips over to zero)
4) The number of framing errors detected by the
node.(counts up to 255 then flips over to zero)
5) Firmware Revision Number
6) EEPROM status 0 = OK, 101 = Corrupted
7) State of the Comms Lock
8) Not used but transmitted
9) Not used but transmitted
10) Not used but transmitted
N.B. Addresses 01 to 04 are common to M550, M560
MultiDin and MultiGen.
4.3.9 Password Code Numbers.
If M550 is being used with Multitek M550 software all rel-
evant codes are detailed in section 2. If user is using other
software, the codes required are as follows :-
General Password 18902
Calibration Enable 17901*
Comms Lock 20904*
Eprom Reset 19903*
* Note General pass code has to be sent first.
Examples of typical packets
Reset EEPROM
[01][10][002C][0002][04][469B7E00][B4E5]
General Passcode
[01][10][0042][0002][04][4693AC00][EE23]
Reset Energy
[01][10][0010][0002][04][00000000][F2A3]
Reset Demand
[01][10][0012][0002][04][00000000][737A]
Calibration Passcode
[01][10][0044][0002][04][468BDA00][C86E]
Comms Lock
[01][10][0060][0002][04][46A35000][2CED]
All values are in Hexadecimal.
M550MAN.PM5 01/08/101, 12:4845