Specifications
19
ACTION : None
COMMENTS : Divisor set
for 1. This means after every
1 unit that M550 counts the
relay pulses once.
ACTION : Select Divisor
required.
COMMENTS : Using the up
and down cursor you can
scroll through the divisor
values available. If a
divisor value of 100 is
required select 100 and
Click on OK.
2.16 The M550 measures Wd (Average Watt Demand
Import & Export) VAd (Average VA Demand ) Ad
(Average Amp Demand) Max Wd (Maximum Watt Demand
Import & Export) Max VAd (Maximum VA Demand) Max
Ad (Maximum Amp Demand). Demand times between 3
and 30 minutes can be programmed in 1 minute steps.
The M550 samples the instantaneous values for 1 minute
then takes the average of these samples and updates the
memory. This sampling and updating every minute
continues until the time period selected is reached. e.g. If
time period is 15 minutes then after 15 minutes the average
of 15 minute demand is displayed. When the 16th minute is
reached the M550 takes the average of minute 2 to 16 and
updates the memory. The Maximum Demand is the highest
value recorded by M550 from being powered up. This value
is retained until either registers are reset or auxiliary power
is removed.