Specifications

59
SITE MANAGEMENT • GENERAL SETUP
TECHNICAL SUPPORT 978-486-0086 • support@burk.com • www.burk.com
COMMANDS OUTPUT
The command output channels are programmed
in the Commands Output Table. To open the
Output Table window, double-click on the
Commands icon in the General Setup window.
The following parameters can be edited:
Type
There are two possible types of command outputs: Momentary
should be selected if the command signal sent lasts only as long
as the Delay setting has been configured. Latching should be
selected if the command signal sent stays active until changed by
another command. Ignores the delay setting.
Delay
The amount of time, definable to 1/10 second increments up to
25.5 seconds, that a momentary command output is activated.
Command channels A and B are mutually exclusive. When
channel A is active, channel B will be inactive. When channel B is
active, channel A is inactive.
A Name
The label displayed by monitoring
software when a channel’s last
command output activation was the
A state.
B Name
The label displayed by monitoring
software when a channel’s last
command output activation was the
B state.
One you have made your changes, click
on the Apply button or the blue Upload
Component button to upload the
changes to your VRC unit.