Specifications
sigmadue - IEC 61131-3 Function Block Library
76
2-3-15 bAI08TC
FB Prototype
bAI08TC
Input parameters
Output parameters
Description
This Function Block sets the chosen input type (see the table below), acquires the
input data from the module and returns the value using the "ChX" signals in engi-
neering units (°C or mV). As inputs the FB wants the network connection, the
node identifier and the type of the sensors connected.
Label Type Description
Network DWORD CAN Network Connection
NodeID USINT CANopen Device Identifier
Ch1Type ASCON_SENSOR Input Type Channel 1 (default value = TCJ)
Ch2Type ASCON_SENSOR Input Type Channel 2 (default value = TCJ)
Ch3Type ASCON_SENSOR Input Type Channel 3 (default value = TCJ)
Ch4Type ASCON_SENSOR Input Type Channel 4 (default value = TCJ)
Ch5Type ASCON_SENSOR Input Type Channel 5 (default value = TCJ)
Ch6Type ASCON_SENSOR Input Type Channel 6 (default value = TCJ)
Ch7Type ASCON_SENSOR Input Type Channel 7 (default value = TCJ)
Ch8Type ASCON_SENSOR Input Type Channel 8 (default value = TCJ)
Label Type Description
Confirm BOOL Function Block Confirm
Ch1 REAL Input1 in Engineering Units
Ch2 REAL Input2 in Engineering Units
Ch3 REAL Input3 in Engineering Units
Ch4 REAL Input4 in Engineering Units
Ch5 REAL Input5 in Engineering Units
Ch6 REAL Input6 in Engineering Units
Ch7 REAL Input7 in Engineering Units
Ch8 REAL Input8 in Engineering Units
NETWORK
NODEID
CH1TYPE
CH2TYPE
CH3TYPE
CH4TYPE
CH5TYPE
CH6TYPE
CH7TYPE
CH8TYPE
DWORD
USINT
ASCON_SENSOR
ASCON_SENSOR
ASCON_SENSOR
ASCON_SENSOR
ASCON_SENSOR
ASCON_SENSOR
ASCON_SENSOR
ASCON_SENSOR
¡
¡
¡
¡
¡
¡
¡
¡
¡
¡
BOOL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
CONFIRM
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
¡
¡
¡
¡
¡
¡
¡
¡
¡