Specifications
sigmadue - IEC 61131-3 Function Block Library
174
Output
PORT
X1 = Communication Port X1 RS232
X3 = Communication Port X3 RS232
X4 = Communication Port X4 RS485 (default value)
PROTOCOL
ASCII = Serial ASCII interface
SLAVE1 = Modbus SLAVE_1 Agent (default value)
SLAVE2 = Modbus SLAVE_2 Agent
MASTER= Modbus MASTER Agent
BAUD
B2400 = 2.4 kbps
B4800 = 4.8 kbps
B9600 = 9.6 kbps (default value)
B19200 = 19.2 kbps
B38400 = 38.4 kbps
B57600 = 57.6 kbps
B115200 = 115.2 kbps
PARITY
NOPAR = NONE (default value)
EVEN = EVEN
ODD = ODD
STOP 1 or 2 (default value = 1)
DATA 7 or 8 (default value = 8)
T_OUT 0... 65535. Deafult value 10 (1000 ms)
Label Options
ERCODE
0 = Communication OK
1 = Port not available
2 = Protocol not available
3 = Invalid configuration
Label Options