Specifications

Chapter 1 - AsconACLib
7
1-3-4 ALARM_DEVIATION MODULE
FB Prototype
ALARM_DEV
Input parameters
Output parameters
Description
This function block generates only independent DEVIATION high and low alarms.
Alarm description
Default values
Label Type Description
VALUE REAL Input value
REF REAL Reference value
DEV_HIGH REAL Deviation Alarm Max
HY_DHIGH REAL Hysteresis Deviation Alarm Max
DEV_LOW REAL Deviation Alarm Min
HY_DLOW REAL Hysteresis Deviation Alarm Min
Label Type Description
DEV_H BOOL Deviation High Alarm
DEV_L BOOL Deviation Low Alarm
VALUE
REF
DEV_HIGH
HY_DHIGH
DEV_LOW
HY_DLOW
REAL
REAL
REAL
REAL
REAL
REAL
¡
¡
¡
¡
¡
¡
BOOL
BOOL
DEV_H
DEV_L
¡
¡
Alarm Type Description
Deviation High
The output DEV_H is active if it is TRUE the condition
VALUE > (REF +( DEV_HIGH + HY_DHIGH))
Deviation Low
The output DEV_L is active if it is TRUE the condition
VALUE < (REF + (DEV_LOW - HY_DLOW))
Input Default values
VALUE 0.0
REF 0.0
ABS_HIGH 0.0
HY_AHIGH 1.0
ABS_LOW 0.0
HY_ALOW 1.0
Output Default values
DEV_H FALSE
DEV_L FALSE