Specifications
sigmadue - IEC 61131-3 Function Block Library
110
the
OUTC
and the
OUTH
output are 0. When it is negative, the opposite
occurs; for each value included in the dead band (now named cross band),
both the
OUTC
and the
OUTH
are different from 0.
• If
DTRK
(Track) is active, the outputs are set according to the value of the
analog input
TRK
. This signal has a range from
[-100.0 … +100.0]
and it
drives both
OUTH
and
OUTC
. When its value is in the range -100.0...0, it
means that a Cool action must be taken; therefore,
OUTH
is set to 0.0, while
OUTC
is set to the value of
TRK
, with the sign inverted. Inversely, when it is
in the range 0…100.0,
OUTC
is set to 0.0, while
OUTH
is set to
TRK
.
Please note that the tracking value is not affected by the
DBND
parameter.
• If the
DAM
input is active (and
DTRK
is inactive) the outputs are set
according to the value of the analog input
AM_VAL
. This signal has a
range from
[-100.0...+100.0]
and it drives both
OUTH
and
OUTC
. When its
value is in the range -100.0...0, it means that a Cool action must be taken;
therefore,
OUTH
is set to 0.0, while
OUTC
is set to the value of TRK, with
the sign inverted. Inversely, when it is in the range 0...100.0,
OUTC
is set
to 0.0, while
OUTH
is set to
TRK
. These values are valid if the
DBND
of the
phase splitter is set to 0.0, otherwise they slightly change.
•If
DAUX
(
Aux
) is active(and both
DAUX
and
DTRK
are inactive), the
outputs are set according to the value of the analog input
AUX
. This signal
has a range from
[-100.0...+100.0]
and it drives both
OUTH
and
OUTC
.
When its value is in the range -100.0...0, it means that a Cool action must
be taken; therefore,
OUTH
is set to 0.0, while
OUTC
is set to the value of
AUX
, with the sign inverted. Inversely, when it is in the range 0...100.0,
OUTC
is set to 0.0, while
OUTH
is set to
AUX
. These values are valid if the
DBND
of the phase splitter is set to 0.0, otherwise they slightly change.