Specifications

DCA-10SPX3 A.C. GENERATOR — PARTS & OPERATION MANUAL — REV. #1 (03/31/01) — PAGE 39
DCA-10SPX3 — MAINTENANCE
INSPECTION / MAINTENANCE
10 Hrs
DAILY
250 Hrs 500 Hrs 1000 Hrs
ENGINE
Check Engine Fluid Levels X
Check Air Cleaner X
Check Battery Acid Level X
Check Fan Belt Condition X
Check for Leaks X
Check for Loosening of Parts X
Replace Engine Oil and Filter *
1
X
Clean Air Filter X
Drain Bottom of Fuel Tank X
Clean Unit, Inside and Outside X
Change Fuel Filter *
2
X
Clean Radiator and Check Coolant Protection
Level
X
Replace Air Filter Element X
Change Corrosion Resistor X
Check all Hoses and Clamps X
Clean Inside of Fuel Tank X
GENERATOR
Measure Insulation Resistance Over 3M ohms
X
*
1
Replace engine oil anf filter at 100 hours, first time only.
*
2
Replace fuel filter at 250 Hours, first time only.
Generator Storage
For storage of the generator for over 30 days, the following
is required:
l Fill the fuel tank completely.
l Completely drain the oil from the crankcase and refill
with fresh oil.
l Clean all external parts of the generator with a cloth.
l Cover the generating set and store in a clean, dry place.
Table of Contents