user manual
GENERATOR SHUT-DOWN PROCEDURES
To shutdown the generator, use the following procedure:
1.  Place both the  circuit breakers 
as shown in Figure 54 to the OFF position..
Figure 54. Main, GFCI and Load 
Circuit Breakers Off
2.  Place the engine speed switch (Figure 55) in the “” 
(down) position..
Figure 55. Ignition Switch (Normal)
3.  Let the engine cool by running it at low speed for 3-5 
minutes with no load applied.
4.  Place the  (Figure 56) to the 
 position.
Figure 56. MPEC Control Switch (Off/Reset)
5.  Verify that all status LEDs on the MPEC display are 
OFF (not lit). 
6.  Remove all loads from the generator.
7.  Inspect entire generator for any damage or loosening of 
components that may have occurred during operation.
1.  Place the  (Figure 56) in the 
 position.
  WARNING
 stop the engine suddenly except in an 
emergency. 
12.  The  coolant temperature gauge (Figure 50) will 
indicate the coolant temperature. Under normal 
operating conditions the coolant temperature should 
be between 167°~203°F (75°~95°C) (Green Zone).
Figure 50. Coolant Temperature Gauge
13.  The tachometer gauge (Figure 51) will indicate the 
speed of the engine when the generator is operating. 
Under normal operating conditions this speed is 
approximately 1800 RPM’s.
Figure 51. Engine Tachometer Gauge
14.  Place the  circuit breakers in the 
ON position (Figure 52).
Figure 52. Main, Aux. and GFCI 
Circuit Breakers (ON)
15.  Observe the generator’s ammeter (Figure 53) and 
verify it reads the anticipated amount of current with 
respect to the load. The ammeter will only display a 
current reading if a load is in use.
Figure 53. Ammeter (Load)
16.  The generator will run until manually stopped or an 
abnormal condition occurs.










