User's Manual

PAGE 36 — DCA250SSI/DCA250SSIU GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (01/12/11) 
GENERATOR START-UP PROCEDURE (AUTO MODE)
STARTING (AUTO MODE)
 DANGER
Before connecting this generator to any 
building’s electrical system, a licensed 
electrician must install an isolation 
(transfer) switch. Serious damage to 
the building’s electrical system may occur 
without this transfer switch.
 CAUTION
When connecting the generator to a isolation (transfer) 
switch, ALWAYS have power applied to the generator’s 
internal battery charger. This will ensure that the engine 
will not fail due to a dead battery.
NOTICE
When the generator is set in the AUTO mode, the 
generator will automatically start in the event of 
commercial power falling below a prescribed level 
by means of a contact closure that is generated 
automatically by a transfer switch.
 WARNING
When running the generator in the AUTO mode, 
remember the generator can start up at any time without 
warning. NEVER attempt to perform any maintenance 
when the generator is in the auto mode.
 CAUTION
The engine speed switch must be set to the “High” 
position when running in the auto-start mode. Failing 
to set the switch in the proper position can result in 
damage to your generator when it turns on.
NOTICE
When the MPEC control switch is placed in the AUTO 
position, the engine glow plugs will be warmed and the 
engine will start automatically. 
When starting generator in AUTO mode use the “Manual 
Start-up” procedure except where noted (see below).
1.  Perform steps 1 through 5 in the Before Starting section 
as outlined in the Manual Starting Procedure.
2. Place the engine speed switch (Figure 52) in the 
HIGH position 
Figure 52. Engine Speed Switch (High)
3. Place the MPEC Control Switch (Figure 53) in the 
AUTO position.
Figure 53. MPEC Control Switch (AUTO)
4.  Continue operating the generator as outlined in the 
Manual Start-up procedure (start at step 5).










