Portable Generator User Manual
PAGE 22 —MQP20P STANDBY GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (11/28/11) 
LOAD APPLICATION/GENERATOR OUTPUT
SINGLE PHASE LOAD
Always be sure to check the nameplate on the generator 
and equipment to insure the wattage, amperage, frequency, 
and voltage requirements are satisfactorily supplied by the 
generator for operating the equipment.
Generally,  the  wattage  listed  on  the  nameplate  of  the 
equipment  is  its  rated  output.  Equipment  may  require 
130—150% more wattage than the rating on the nameplate, 
as the wattage is influenced by the efficiency, power factor 
and starting system of the equipment.
.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 1.0. See Table 6 below 
when connecting loads.
Table 7. Cable Selection (60 Hz, Single Phase Operation)
Current 
in 
Amperes 
Load in Watts Maximum Allowable Cable Length
At 100 
Volts
At 200 
Volts
#10 Wire #12 Wire #14 Wire #16 Wire
2.5 300 600 1000 ft. 600 ft. 375 ft. 250 ft.
5 600 1200 500 ft. 300 ft. 200 ft. 125 ft.
7.5 900 1800 350 ft. 200 ft. 125 ft. 100 ft.
10 1200 2400 250 ft. 150 ft. 100 ft.
15 1800 3600 150 ft. 100 ft. 65 ft.
20 2400 4800 125 ft. 75 ft. 50 ft.
CAUTION: Equipment damage can result from low voltage
NOTICE
If wattage is not given on the equipment’s name plate, 
approximate wattage may be determined by multiplying 
nameplate voltage by the nameplate amperage.
Table 6. Power Factor By Load
Type of Load Power Factor
Single-phase induction motors 0.4-0.75
Electric heaters, incandescent lamps 1.0
Fluorescent lamps, mercury lamps 0.4-0.9
Electronic devices, communication 
equipment
1.0
Common power tools 0.8
An inadequate size connecting cable which cannot carry 
the required load can cause a voltage drop which can burn 
out the appliance or tool and overheat the cable. Refer to 
Table 7 to select the correct cable size.
  When  connecting  a  resistance  load  such  as  an 
incandescent lamp or electric heater, a capacity of up to 
the generator’s rated output (kW) can be used.
  When  connecting  a  fluorescent  or  mercury  lamp,  a 
capacity  of  up  to  the  generator's  rated  output  (kW) 
multiplied by 0.6 can be used.
  When connecting an electric drill or other power tools, 
pay  close  attention  to  the  required  starting  current 
capacity.
When connecting ordinary power tools, a capacity of up to 
the generator’s rated output (kW) multiplied by 0.8 can be 
used.
Generator Amperage
Table  8  shows  the  maximum  amps  the  generator  can 
provide. DO NOT exceed the maximum amps as listed.
NOTICE
Motors and motor-driven equipment draw much greater 
current for starting than during operation.
 DANGER
Before  connecting  this  generator  to  any  building’s 
electrical system, a licensed electrician must install 
a transfer switch. Serious damage  to the building’s 
electrical system may occur without this transfer switch.
Table 8. Generator Maximum Amps
Rated Voltage Maximum Amps
1Ø 120 Volt 83 X 2 amps (4 wire)
1Ø 240 Volt 83 amps (4 wire)










