Portable Generator User Manual
PAGE 20 —MQP20P STANDBY GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (11/28/11) 
DIGITAL CONTROLLER PANEL
Figure 5. Digital Controller Components
RUN OFF
AUTO
LOAD
TEST
Vavg
600
Aavg
508
Freq
60.0
Microprocessor Engine Controller
MEC 20
ALARM
SHUTDOWN
EMERGENCY
STOP
READY
SPEED SIGNAL
LAMP TEST
SILENCE
RESET
DECREMENT INCREMENT
EXIT
ENTER
1
13
14
2
3
6
8
9
10
11
4
5
12
7
FREQUENCY
ADJUST
VOLTAGE
ADJUST
15 16
1.  Liquid Crystal Display — Displays voltage, amperage, 
frequency,engine information, fault warnings, and other 
generator and engine information.
2.  EXIT Pushbutton — Press button to scroll backwards 
through the  status menus  or programming prompts. 
Press  and  hold  for  approximately 2  seconds  to  exit 
programming menu when in the programming mode.
3.  DECREMENT Pushbutton — Press button to change 
a  programming  value  while  in  the  programming 
mode. Press and hold this button to decrease value 
continuously  and  release  when  desired  value  is 
displayed. NOTE: The longer the button is held down, 
the faster the value will decrease.
4.  INCREMENT Pushbutton — Press button to change 
a programming value while in the programming mode 
or to select a desired programming menu loop. Press 
and hold this button to increase value continuously and 
release when desired value is displayed. NOTE: The 
longer the  button is  held down, the  faster the  value 
will increase.
5.  ENTER Pushbutton — Press button to scroll through 
the  status  menus  or  programming  prompts. This 
button is used to enter a programming mode as well 
as  accepting  changed  programming  values.  NOTE: 
The longer the button is held down, the faster the next 
menu prompt will appear.
6.  RUN Pushbutton and LED — Press button to initiate 
a manual start signal to the generator. The LED will 
light when in RUN mode.
7.  OFF Pushbutton and LED — Press button to initiate 
a stop signal to the generator. The LED will light when 
in OFF mode.
8.  AUTO Pushbutton and LED — Press button to initiate 
automatic operation of the generator. The LED will light 
when in AUTO mode.
9.  LOAD TEST Pushbutton and LED — Press button to 
initiate load test of the generator when connected to 
an associated transfer switch. The LED will light when 
in LOAD TEST mode.
10.  EMERGENCY STOP Pushbutton and LED — Press 
button  to  initiate  an  emergency  stop  signal  to  the 
generator.
11.  READY LED — Lights when the generator is set for 
automatic operation and no shutdown or alarm faults 
have been activated.
12.  SPEED SIGNAL LED — Lights when the engine speed 
signal is detected.
13.  ALARM  LED  —  Lights  when  any  pre-programmed 
alarm fault has been activated.
14.  SHUTDOWN  LED  —  Flashes when  any  pre-
programmed shutdown fault has been activated.
15.  FREQUENCY ADJUST — This screwdriver adjustable 
potentiometer is used to fine tune the roll-off frequency 
from 54 to 61 Hz.
16.  VOLTAGE  ADJUST  — This  screwdriver  adjustable 
potentiometer is used to fine tune the generator output 
voltage.