Portable Generator User Manual
MQP20P STANDBY GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (11/28/11) — PAGE 15
INSTALLATION
OUTDOOR INSTALLATION
Install  the  generator  in  a  area  that  is  free  of  debris, 
bystanders,  and  overhead  obstructions.  Make  sure  the 
generator is on secure level ground so that it cannot slide 
or shift around. Also install the generator in a manner so 
that the exhaust will not be discharged in the direction of 
nearby homes.
The installation site must be relatively free from moisture 
and  dust.  All  electrical  equipment  should  be  protected 
from  excessive  moisture.  Failure  to  do  so  will  result  in 
deterioration of the insulation and will result in short circuits 
and grounding.
Foreign  materials  such  as  dust,  sand,  lint and  abrasive 
materials  have  a  tendency  to  cause  excessive  wear  to 
engine and alternator parts.
INDOOR INSTALLATION
Exhaust  gases  from  diesel  engines  are  extremely 
poisonous. Whenever  an  engine is  installed  indoors the 
exhaust fumes must be vented to the outside. The engine 
should be installed at least two feet from any outside wall. 
Using an exhaust pipe which is too long or too small can 
cause excessive back pressure which will cause the engine 
to heat excessively and possibly burn the valves.
MOUNTING
The generator must be mounted on a solid foundation (such 
as  concrete)  and set  firmly  on  the  foundation to  isolate 
vibration of the generator when it is running. The generator 
must sit at least 6 inches above the floor or grade level (in 
accordance to NFPA 110, Chapter 5-4.1).
 CAUTION
Pay close attention to ventilation when operating the 
generator inside tunnels and caves. The engine exhaust 
contains noxious elements. Engine exhaust must be 
routed to a ventilated area.
GENERATOR GROUNDING
To guard against electrical shock and possible damage to 
the equipment, it is important to provide a good EARTH 
ground.
Article  250  (Grounding)  of  the  National  Electrical  Code 
(NEC)  provides  guidelines  for  proper  grounding  and 
specifies that the cable ground shall be connected to the 
grounding system of the building as close to the point of 
cable entry as practical.
NEC  articles  250-64(b)  and  250-66  set  the  following 
grounding requirements:
1.  Use  one  of  the  following  wire  types  to  connect  the 
generator to earth ground.
a.  Copper — 8 AWG (5.3 mm
2
)
b.  Aluminum — 6 AWG (8.4 mm
2
)
2.  When grounding the generator (Figure 2) connect the 
ground cable between the lock washer and the nut on 
the  generator and  tighten  the  nut fully.  Connect  the 
other end of the ground cable to earth ground.
3.  NEC article 250-52(c) specifies that the earth ground rod 
should be buried a minimum of 8 ft. into the ground.
NOTICE
When connecting the generator to any building electrical 
system, ALWAYS consult a licensed electrician.










