Generator Maintenance, Inspection and Repair Services Bid Number 6000001312
California Department of Corrections and Rehabilitation (CDCR) Exhibit A
SCOPE OF WORK
Page 8 of 18
k) Megger Testing
Perform megohmeter testing to check the insulation integrity of the
windings in the generator.
9. GENERATOR CONTROL PANEL
a) Start Controls (Manual and Automatic)
Check for proper operation.
Check automatic start.
b) Voltmeter
Check for correct readings.
Check voltage level.
c) Ammete
Check for correct readings while system is under load.
d) Frequency Meter
Check for correct readings under load and with no load conditions.
e) Circuit Breakers
Inspect free movement of circuit breakers and tight connections.
f) Control Panel
Vacuum/clean engine generator set control panel.
g) Connection Enclosure
Vacuum/clean engine generator set connection enclosure.
10. GENERATOR AC POWER DISTRIBUTION SYSTEM
a) Automatic Transfer Switch Test
Test automatic transfer switch (ATS) for correct operation by simulating a
utility power supply failure.
Check for correct sequential operation of the ATS.
Recording of utility AC voltage at ATS connections.
Recording of engine generator set AC voltage at the ATS connections.
Observation and logging of time elapsed between loss of utility AC power
and the restoration of AC power to the facility emergency load by the
facility EPSS.
Vacuum/clean automatic transfer switch enclosure.
B.
The Contractor shall remove and dispose of used oil, coolant, and any other used
liquids that result from service and ensure area is returned to its original condition at
the time service began. The Contractor shall provide:
QUARTERLY SERVICES
1) Visual inspection for coolant, oil, vacuum, and fuel leaks.
Bid 6000001312