Specifications

DCA70SSJU4i — LOAD BANK INSTRUCTIONS P/N EE58627 — REV. #1 (03/13/15) — PAGE 7
OUTPUT TERMINAL PANEL (UVW-GND.) WIRE
CONNECTIONS
1. Connect the four 10 AWG wires RED, BLACK BLUE
and GREEN to the rear of the ouput terminal panel as
shown in Figure 13 and Table 5.
2. Once all four wires have been securely connected to
the rear of the output terminal panel, re-install output
terminal panel enclosure.
DC CONTROL SPLIT LOOM HARNESS (CONTACTOR
J-BOX SIDE)
There are six wires, (P/N EE58517) that need to be
connected to the Contactor J-Box. Connect the wires as
shown below.
1. Insert the 6 wires into the 3/8", 54-inch DC Control
split-loom harness (P/N EE58517).
2. Once the wires have been inserted into the split-loom
harness secure using tie-wraps.
3. One side of this harness (Figure 14) has 6 wires with
the insulation stripped back 1/2-inch. The other side
has 3 terminal rings attached to the wires.
Figure 14. DC Control Split Loom Harness
4. Route the split-loom harness through the front right
cable connector bushing on the Contactor J-Box. Be
sure to route only the stripped wires up to the J-Box
not the terminal ring side.
5. Connect the six wires to the Contactor J-Box as shown
in Figure 15 and Table 6.
Table 5. UVW-GND Output Terminal Wiring
Function Color
U RED
V BLACK
W BLUE
O
1
N/A
GND. GREEN
1
Terminals O and GND. are bonded
TO CONTACTOR
J-BOX (TB1)
TO ECU,CTRL. BX.
VOL
TAGE SEL. SW.
DC CONTROL
3/8” SPLIT-LOOM
HARNESS
P/N EE58517
5 FT
Figure 15. DC Control Wiring (TB1)
Table 6. DC Control Wiring
Color
Contactor J-Box
Terminal
Destination
BROWN TB1-1 ECU Pin-57
RED TB1-2 ECU Pin-16
RED TB1-2 VS Switch Pin-42
RED/WHT TB1-3 10 AMP Fuse
GRN/WHT TB1-4 Ground (Ctrl. Bx.)
YELLOW TB1-5 ECU Pin-13
TB1
1
2
3
4
4
4
2
3
1
4
4
4
DC CONTROL
3/8” SPLIT-LOOM
HARNESS
P/N EE58517
BRN
CONTACTOR
J-BOX
ALL WIRES
16 AWG.
5
5
1
2
3
4
4
4
2
3
1
4
4
4
5
5
6-WIRES
TO ECU,CTRL. BX.
VOLTAGE SEL. SW.
RED
YEL
RED/
WHT
GRN/
WHT