Instruction Manual
GENERATOR OUTPUTS
A wide range of voltages are available to supply voltage for 
many different applications. Voltages are selected by using 
the voltage selector switch (Figure 12). To obtain some of 
the voltages as listed in Table 7 (see below) will require a 
fine adjustment using the voltage regulator (VR) control 
knob located on the control panel. 
The voltage selector switch (Figure 12) is located above 
the output terminal panel’s Hard Wire Hook-up Panel. It 
has been provided for ease of voltage selection..
Figure 12. Voltage Selector Switch
 CAUTION
 change the position of the voltage selector 
Switch while the engine is running.  place 
circuit breaker in the OFF position before selecting 
voltage
3Ø
 
208V 220V 240V 416V 440V 480V
1Ø  120V 127V 139V 240V 254V 277V
1Ø 
120V
Line-Neutral
N/A N/A
240V
Line-Line
N/A N/A
Table 8 shows the maximum amps the generator can 
provide. DO NOT exceed the maximum amps as listed.
The load capability of the GFCI receptacles is directly 
related to the voltage being supplied at either the output 
terminals or the three twist lock auxiliary receptacles.
Figure 15 and Table 10 show what amount of current is 
available at the GFCI receptacles when the output terminals 
and twist lock receptacles are in use. Be careful that your 
load does not to exceed the available current capability at 
the receptacles.
 
1Ø 120 Volt
100 amps (4 wire)
108 amps X 2 (Zigzag)
1Ø 240 Volt
50 amps (4 wire)
108 amps (Zigzag)
3Ø 240 Volt 108 amps
3Ø 480 Volt 54 amps
KW in Use
1Ø 240/120V
GFCI Duplex
5-20R 120V
26 0
24.8 5 amps/receptacle
23.6 10 amps/receptacle
22.4 15 amps/receptacle
21.2 20 amps/receptacle
 
 
3Ø 240/480V
GFCI Duplex
5-20R 120V
45
0 amps/receptacle
40.9
5 amps/receptacle
36.7
10 amps/receptacle
32.6
15 amps/receptacle
28.4
20 amps/receptacle










