OUTPUT TERMINAL PANEL FAMILIARIZATION
Loads can be connected to the generator by various 
methods, output terminal lugs, camlocks or the convenience 
receptacles (Figure 10). Make sure to read the operation 
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole, 
110A main circuit breaker is provided. Make sure to switch 
 circuit breakers to the OFF position prior to starting 
the engine.
Figure 10. Connecting Loads
U
V
W
LOAD
O
NEUTRAL
GROUND
HARD WIRE
HOOKUP PANEL
LOAD
GFCI
RECEPTACLE
LOAD
CS-6369
TWIST-LOCK
RECEPTACLES
CAMLOCKS (OPTION)
Over Current Relay
An over current relay (Figure 11) is connected to the main 
circuit breaker. In the event of an overload, both the circuit 
breaker and the over current relay may trip. If the circuit 
breaker can not be reset, the reset button on the over 
current relay must be pressed. The over current relay is 
located in the control box.
Figure 11. Over Current Relay
NOTICE
Remember the overcurrent relay monitors the current 
flowing from the  
to the load.
In the event of a short circuit or over current condition, 
it will automatically trip the 110 amp main breaker.
To restore power to the Output Terminal Panel, press 
the reset button on the overcurrent relay and place the 
main circuit breaker in the closed position (ON).