Manual

GENERATOR SHUT-DOWN PROCEDURES
To shutdown the generator, use the following procedure:
1. Place both the circuit breakers
as shown in Figure 42 to the OFF position.
Figure 42. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the (Figure 43)
in the position
Figure 43. Switch
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel
are OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
stop the engine suddenly except in an
emergency.
1. Push the Emergency Stop Pushbutton Switch
(Figure 44).
Figure 44. Emergency Stop Button
This unit is equipped with safety devices to automatically stop
the engine in the event of low oil pressure, approximately
14 psi (97 kPa), or high water temperature, approximately
212°F (100° C), overspeed approximately (2,040 rpm). The
alarm lamps on the ECU illuminate to signify the reason
for the shutdown.