Manual

DCA-150SSVU— OPERATION AND PARTS MANUAL (STD)— REV. #1 (06/03/03) — PAGE 45
Shutdown Procedure - Engine Controller
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 44 to the "OFF position".
2. Place the engine speed switch in the “LOW position
(Figure 64).
Figure 64. Engine Speed Switch (Low)
3. Let the engine cool by running it for 3-5 minutes with no
load applied.
4. Place the Auto-Off/Reset-Manual switch (Figure 65) to
the
OFF/Reset
position.
Figure 65. Off/Manual Auto Switch (Off)
5. Verify that the
all
status LED on the MPEC display
(Figure 52) are "OFF" (not lit).
6. Remove all loads from the generator.
NEVER stop the engine suddenly except
in an emergency. DO NOT use the
emergency stop switch a as method of
shutting down the generator. This switch is
ONLY to be used in the event of an
emergency.
CAUTIONCAUTION
CAUTIONCAUTION
CAUTION
:
Emergency Shutdown Procedure - Engine Controller
1. To shut-down the engine in the event of an
emergency, switch the
MAIN
,
GFCI
and
LOAD
(Figure 44) circuit breakers to “OFF” position.
2. Place the Auto-Off/Reset-Manual switch (Figure 65)
to the “OFF/Reset“ position.
DCA-150SSVU — GENERATOR SHUT-DOWN PROCEDURE