Specifications
3Ø, 600 VAC can be achieved via the auto-transformer
module. This module provides the necessary electronics
to convert the 3Ø, 480 VAC inut voltage to a 3Ø, 600 VAC
output voltage.
The 3Ø, 600 VAC ouput voltage cannot be achieved unless
the voltage selector switch (Figure 28) is placed in the 3Ø,
480/277 position.
Figure 28. Voltage Selector Switch
3Ø-480/277V Position (600 VAC Auto-Transformer)
1. Loosen the latches on the control box enclosure and
open the door.
2. Drill a 1-1/2 inch hole at the bottom of the control box
enclosure as shown in Figure 29.
Figure 29. Control Box Enclosure (Drilling
DANGER
When connecting the load wires make sure the
generator is The possibility of electrocution exists
causing severe bodily harm even death!
CIRCUIT BREAKER
ENCLOSURE
DRILL
NEW HOLE
(1-1/2” DIA.)
STRAIGHT
FITTING
LOCK
RING
BUSHING
600 VAC CONNECTIONS
3. After drilling, make sure all shavings and debris have
been removed from the enclosure.
4. Install customer supplied conduit, fittings and bushing
through enclosure hole opening.
5. Next, route the customer supplied 5 wires through the
straight conduit fitting.
6. Connect the 3 load wires (RED, and )
to the load side (bottom) of the circuit breaker, T1, T2
and T3 respectively. Reference Figure 30
Figure 30. Control Box Enclosure
Load Connections
7. Connect the neutral wire ( to the neutral bus
bar.
8. Connect the ground wire (GREEN) to the ground
terminal.
9. Torque all wires to 45 lbf-in (5 N
.
m).
10. Once all wires have been securely tighten, close
control box enclosure door and securely tighten the
control box door latches.
L1
T1
T2
T3
L2
L3
70 AMP
CIRCUIT BREAKER
LOAD
WIRES
FROM
600 VAC
AUTO
TRANSFORMER
NEUTRAL BUS BAR
GROUND
TERMINAL