Cut Sheet
ANDERSON
™
HUBBELL
®
POWER SYSTEMS FARGO
® APRIL 2014
5
SPLICES
FORMED WIRE
GUY WIRE
For repairing damaged or severed guy wire or messenger cable.
Do not use FWLS splices on overhead shield wires.
Fargo FWLS series formed wire are designed for use on all types of galvanized guy wire (EHS, High Strength,
Common, Siemens-Martin, Utilities, and Bell System Strand).
FWLS will hold a minimum of 100% of the guy wire rated breaking strength (ultiate strength) when centered over the
severed or point of damage.
Note: Consult factory for information on use if damaged area exceeds length of splice.
Left hand lay standard.
NOTES: All dimensions: inches (mm) unless otherwise noted.
Rated at full tension of guy strand RBS for EHS, HS, Siemens-Martin, Common, and Utility Grades.
GALVANIZED STEEL
FWLS
CATALOG
NUMBER NOMINAL SIZE
MAXIMUM
RBS
LB (KN)
NOMINAL LENGTH (L) DIAMETER RANGE IN (MM)
NUMBER
OF
SUBSETS
COLOR
CODE
PACKAGING PER BOX
IN MM MIN MAX UNITS
WEIGHT
LBS. (KG)
FWLS2102 3/16” (3W & 7W) 3,990 (17.7) 27 685 0.174 (4.41) 0.203 (5.16) 2 Red 100 30 (13.6)
FWLS2103 7/32” (7W) 5,400 (24.0) 29 737 0.204 (5.18) 0.230 (5.84) 2 Green 100 36 (16.3)
FWLS2104 1/4” (3W & 7W) 6,650 (29.6) 35 889 0.231 (5.87) 0.259 (6.58) 2 Yellow 50 34 (15.4)
FWLS2105 9/32” (7W) 8,950 (39.8) 38 965 0.260 (6.60) 0.291 (7.39) 2 Blue 50 36 (16.3)
FWLS2106 5/16” (3W & 7W) 11,200 (49.8) 42 1067 0.292 (7.42) 0.336 (8.53) 2 Black 50 46 (20.8)
FWLS2107 3/8” (3W & 7W) 15,400 (68.5) 50 1270 0.337 (8.56) 0.394 (10.01) 3 Orange 25 38 (17.2)
FWLS2108 7/16” (7W) 20,800 (92.5) 56 1422 0.395 (10.03) 0.474 (12.04) 3 Green 25 58 (26.3)
FWLS2109 1/2” (7W & 19W) 26,900 (119.7) 63 1600 0.475 (12.07) 0.515 (13.08) 3 Blue 10 36 (16.3)
FWLS2110 9/16” (7W & 19W) 35,000 (155.7) 71 1803 0.516 (13.11) 0.570 (14.48) 3 Yellow 10 52 (23.5)
FWLS