Cut Sheet
Conductor Stranding* Nominal O.D.
(mils)
Allowable Ampacities+ Approx. Net Weight per 1000’
(Ibs)
Standard
Package
Size/Const. (AWG or
kcmil)
Phase
Conductor &
Neutral
Equipment
Ground
Conductor
60°C 75°C 90°C Dwelling
SER Aluminum Two Conductor With Bare Ground (Formerly referred to as “EZ-SE”)
6-6-6 7 -- 650 40 50 60 -- 150 B
4-4-4 7 -- 745 55 65 75 -- 203 B
4-4-6 7 -- 745 55 65 75 -- 203 B
2-2-2 7 -- 864 75 90 100 100 290 B
2-2-4 7 -- 864 75 90 100 100 290 B
2/0-2/0-1 12 -- 1140 115 135 150 150 527 B
2/0-2/0-2/0 12 -- 1140 115 135 150 150 527 B
4/0-4/0-2/0 19 -- 1354 150 180 205 200 784 C
4/0-4/0-4/0 19 -- 1354 150 180 205 200 784 C
SER Three Conductor With Bare Ground (Formerly referred to as “Four Conductor”)
8-8-8-8 1 1 612 30 40 45 -- 136 B
6-6-6-6 7 7 717 40 50 60 -- 196 B
4-4-4-6 7 7 823 55 65 75 -- 252 B
2-2-2-4 7 7 956 75 90 100 100 359 B
1-1-1-3 8 7 1079 85 100 115 110 449 C
1/0-1/0-1/0-2 10 1 1168 100 120 135 125 540 C
2/0-2/0-2/0-1 12 1 1264 115 135 150 150 653 C
3/0-3/0-3/0-1/0 16 1 1378 130 155 175 175 793 C
4/0-4/0-4/0-2/0 19 1 1503 150 180 205 200 968 C
250-250-250-3/0 22 1 1576 170 205 230 225 -- C
SER Four Conductor With Bare Ground (Formerly referred to as “Five Conductor”)
2-2-2-2-4 6 7 1059 75 90 100 100 452 B
2/0-2/0-2/0-2/0-1 12 1 1404 115 135 150 150 827 C
4/0-4/0-4/0-4/0-2/0 19 1 1672 150 180 205 200 1228 C
250-250-250-250-3/0 22 1 1847 170 205 230 225 -- C
SEU Two Conductor With Bare Concentric Ground (Formerly referred to as “Three Conductor”)
6-6-6 7 8 430 X 687 40 50 60 -- 145 H
4-4-4 7 12 499 X 800 55 65 75 -- 198 I
4-4-6 7 15 474 X 775 55 65 75 -- 181 I
2-2-2 7 14 569 X 925 75 90 100 100 283 I
2-2-4 7 18 554 X 910 75 90 100 100 259 I
2/0-2/0-2/0 18 18 736 X 1221 115 135 150 150 514 CJ
2/0-2/0-1 18 14 720 X 1205 115 135 150 150 468 CJ
AL SE, SER, and SEU