Priority Wire & Cable, Little Rock, AR PWC-2013
Triplex 8000 Series Conductor Aluminum 600V URD
Ampacity 90°C conductor temperatures, 20°C ambient temperature. RHO 90. 100% load factor for three conductor triplex with neutral
carrying only unbalanced load. Ampacity not for NEC applications.
.
Application:
Aluminum 8000 Series 600V URD cable is designed for use in secondary distribution circuits, where installed in duct or
direct burial applications, where increased flexibility is needed. The conductors are rate Type RHHW-2 or USE-2.
Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is 600 volts. As an option,
this cable can provide pre-pulled into duct.
Conductors:
Aluminum 8000 Series 600V URD cable has a concentric strand or compressed AA – 8000 series aluminum conductor.
Conductors are cabled together, with a surface printing for identification. The neutral conductor has a yellow stripe and
sequential footage markings.
Insulation:
Aluminum 8000 Series 600V URD cable has a black cross-linked polyethylene (XLP) insulation.
Standards: UL 44 for type RHW-2
UL 854 for type USE-2
ASTM B-230
ASTM B-231
ASTM B-609
ASTM B-901
ICEA S-105-692
Federal Specification J-C – 30B
Code
Word
Phase Conductor Neutral
Single
Phase
Conductor
Complete
Cable
Weight
lbs./1000
ft.
Allowable Ampacity +
Size
AWG
Stranding
Insulation
Thickness
(mils)
Size
AWG
Stranding
Insulation
Thickness
(mils)
Direct
Burial
In
Duct
Vassar
4 7 60 4 7 60 345 745 191 125
90
Stephens
2 7 60 4 7 60 403 870 249 165
120
Ramapo
2 7 60 2 7 60 403 870 278 165
120
Brenau
1/0 19 80 2 7 60 512 1106 387 215
160
Converse
2/0 19 80 1 19 80 555 1199 478 245
180
Sweetbriar
4/0 19 80 2/0 19 80 658 1421 709 315
240
Monmouth
4/0 19 80 4/0 19 80 658 1421 796 315
240
Pratt
250 37 95 3/0 19 80 732 1581 853 345
265
Wesleyan
350 37 95 4/0 19 80 831 1795 1118 415
320