Cut Sheet
NOTES:
1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerances of ±10%.
3. Two, three or four conductors can be paralleled on a reel.
4. The suffix -2 indicates that these wire types can be used at a continuous 90°C operating temperature in wet and dry locations.
Size
AWG Insulation Conductor USE-2 Conductor
NOMINAL WEIGHT
or kcmil Thickness Diameter Diameter
(lbs./1000 ft.) STANDARD PACKAGE
(Mils) (Inches) (Inches) STABILOY Total Length Reel
6 60 .169 .290 25 44 1000' NRC 16.15
4 60 .213 .335 39 63 1000' NRC 16.15
2 60 .268 .390 62 92 1000' NRC 21.15
1 80 .299 .460 79 122 1000' NRC 21.15
1/0 80 .336 .500 99 148 1000' NRC 21.18
2/0 80 .376 .540 125 179 1000' NRC 24.15
3/0 80 .423 .590 157 217 1000' NRC 24.18
4/0 80 .475 .635 199 265 1000' NRC 27.18
250 95 .520 .710 235 320 1000' NRC 30.18
300 95 .570 .760 282 374 1000' NRC 30.24
350 95 .616 .810 329 428 1000' NRC 30.24
400 95 .659 .850 376 482 1000' NRC 32.24
500 95 .736 .930 469 588 1000' NRC 32.24
600 110 .813 1.035 563 713 1000' NRC 36.24
700 110 .877 1.100 657 818 1000' NRC 40.24
750 110 .908 1.130 704 870 1000' NRC 40.24
900 110 .999 1.239 847 1042 1000' NRC 48.28
1000 110 1.060 1.280 939 1132 1000' NRC 48.28
Description:
USE-2/RHH/RHW–2 is a compact stranded
conductor. Mylar tape may be placed between
the XLPE insulation and the conductor strands.
Application:
Primarily used as Type USE-2 direct-buried underground service
entrance, but is also listed for RHH or RHW-2 making it suitable for
applications in raceways for general purpose lighting and power
circuits. This multiple listing offers a unique advantage to the
installer to purchase one product that is suitable for installation
on both sides of service-point and where service-point is located
within the envelope of the building.
Marking:
Cables will bear the following surface marking: Alcan
(Plant of Manufacture) (Size) Compact STABILOY ® AA-8030 AL
Series XLPE 600 V USE-2 or RHH or RHW-2 SUN-RES (UL)
(Year of Manufacture).
Available Options:
Contact Alcan Cable for:
1. 600V RHH or RHW-2 conductors rated for
"CT USE" and other markings.
2. 2000V RHH or RHW-2 conductors
3. 2000V RHH or RHW-2 conductors rated for
"CT USE" and other markings.
Type USE-2/RHH/RHW-2