Cut Sheet

USE-2
XLP Insulation
Underground Service Cable
©
2012, Cerro Wire LLC
All Rights Reserved
MADE IN THE USA
Type RHH-90°C (Dry)
Type RHW-2-90°C
(Wet or Dry)
600 volts
APPLICATIONS
For use in conduit or suitable for use as underground service entrance cable for
direct burial per NEC
®
. Good choice for industrial applications where better insulation toughness and
resistance to moisture and heat are desired. For use as RHH or RHW-2 in wet or dry locations at
temperatures up to 90°C. Sunlight-resistant (black only). For CT use on 1/0 and larger. Gas and Oil
Resistant II.
CONDUCTORS
Stranded conductors: Uncoated, soft copper per ASTM-B3 and ASTM-B8.
INSULATION
XLP (cross-linked polyethylene). Printed with True Sequential Footage.
INDUSTRY STANDARDS*
UL 44 (RHH or RHW-2), File No. E125474
UL 854 (USE-2), File No. E11098
ASTM-B3
ASTM-B8
SURFACE PRINT
Sample (14-10 AWG): CERROWIRE-U 12 AWG (3,31mm
2
) (UL) USE-2 OR RHH OR RHW-2 GRII
600V XL
Sample (8-1 AWG): CERROWIRE-U 2 AWG (33,6mm
2
) (UL) USE-2 OR RHH OR RHW-2 GRII SR
600V XL
Sample (1/0-750 MCM): CERROWIRE-U 400 MCM (203 mm
2
) (UL) USE-2 OR RHH OR RHW-2
GRII SR 600V XL
*For Colors "SR" is omited.
*It is the sole responsibility of the end user to determine suitability of this product for its intended end use and
application.
Sequential
foot markings
Rated for CT use (1/0
and larger)
Sunlight resistant
in black
Underground Cable
A Marmon Wire & Cable/
Berkshire Hathaway Company
REV-05/2012
Electrical Distribution Division: 800.523.3869 | FAX 877.877.9563
Consumer Markets Division: 866.572.3776 | FAX 812.793.2626
www.cerrowire.com
Federal Specification A-A-59544
NFPA70: National Electrical Code
®
NEMA WC70/ICEA S-95-658
RoHS Compliant