Single Aluminum Conductor 600V URD
All values are nominal and subject to correction
Ampacity 90°C conductor temperatures, 20°C ambient temperature. RHO 90. 100% load factor. UL Standard 854 available
upon request. Ampacity not for NEC applications.
.
Application: Aluminum 600V URD cable is designed for use in secondary distribution circuits, where installed in duct or direct
burial applications. Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is
600 volts. As an option, this cable can provided pre-pulled into duct.
Conductors: Aluminum 600V URD cable has a concentric strand or compressed 1350-H19 series aluminum conductor.
Insulation: Aluminum 600V URD cable has a black cross linked polyethylene (XLP) insulation.
Standards: ASTM B-230
ASTM B-609
ICEA S-105-692
RUS ACCEPTED
CodeWord
Conductor
Size
Nominal
Insulation
(mils)
Approx.O.D.
(inches)
EstimatedWeightlbs./1000ft.
Ampacitivity
Directly
Buried
Aluminum Total
Princeton
6
60 0.298 25 44 108
Mercer 4 60 0.345 39 63 140
Clemson 2 60 0.403 62 92 180
Kenyon 1 80 0.473 78 121 203
Harvard 1/0 80 0.512 99 146 231
Yale 2/0 80 0.555 125 177 263
Tufts 3/0 80 0.603 157 215 299
Beloit 4/0 80 0.658 198 263 338
Hofstra 250 95 0.732 234 314 368
Gonzaga
300 95 0.784 281 367 407
Rutgers 350 95 0.831 328 420 444
Dartmouth 400 95 0.875 376 476 475
Emory 500 95 0.956 469 577 540
Duke 600 110 1.060 562 697 595
Furman
700 110 1.127 656 804 645
Sewanee 750 110 1.159 703 853 667
Fordham 1000 110 1.304 937 1108 800