Cut Sheet

Seattle City Light
MATERIAL STANDARD
Schedule 40 PVC Conduit and Fittings
standard number:
superseding:
effective date:
page:
7015.05
April 23, 2009
June 19, 2009
3 of 5
4. Detailed Requirements
4.2 Conduit, continued
Conduit shall meet the following performance requirements:
Table 4.2b
Description
UL 651
Section
tensile strength 07
deflection under heat and load 08
extrusion process 09
low-temperature handling 10
water absorption 11
resistance to crushing 12
resistance to impact 13
flame 14
Description
UL 651
Section
conduit for use with 90 degree C wire 17
resistance to specific reagents 18
sunlight resistance 19
pipe stiffness 20
pull - joint separation 21
bending and pull - joint separation 22
joint water tightness 23
elastomeric materials accelerated aging 24
permanency of printing 25
4.3 Elbows
Table 4.3
Stock
Number
Trade Size,
IPS, in
Degree
Bend
End
#1
End
#2
Radius,
in
734551 0-1/2 90 bell str. cut 04
734671 0-3/4 90 04-1/2
734550 1 90 05-3/4
734546 1-1/4 90 07-1/4
734547 1-1/2 90 08-1/4
90 degree elbow
734548 2 90 24
734549 2-1/2 90 24
734553 1-1/4 45 07-1/4
734554 1-1/2 45 08-1/4
734555 2 45 18
734557 3 45 36
734558 3-1/2 45 36
45 degree elbow
734559 4 45 36
734560 5 45 str. cut 48
010337 6 45 bell 48
734561 2 22-1/2 18
734562 2-1/2 22-1/2 18
734563 3 22-1/2 24
734564 3-1/2 22-1/2 24
22-1/2 degree elbow
734566 4 22-1/2 24
734568 5 22-1/2 str. cut 24
010444 4 5 bell n/a
010443 5 5 bell n/a
5 degree bend