Cut Sheet
Size and Number
of Phase
Conductors
Solid or
Stranded
Grounding/Bonding
Conductor
Nominal Overall
Diameter
(inches)
Weight per 1000'
(lbs)
Allowable Ampacity+ Package Code
60° C 75° C 90° C AD
14/2 Solid 12 Solid
Aluminum
0.400 63 15 15 15 AD
14/2 Stranded 12 Solid
Aluminum
0.405 67 15 15 15 AD
14/3 Solid 12 Solid
Aluminum
0.410 78 15 15 15 AD
14/3 Stranded 12 Solid
Aluminum
0.425 85 15 15 15 AD
14/4 Solid 12 Solid
Aluminum
0.435 96 15 15 15 AD
12/2 Solid 10 Solid
Aluminum
0.430 88 20 20 20 AD
12/2 Stranded 10 Solid
Aluminum
0.437 90 20 20 20 AD
12/3 Solid 10 Solid
Aluminum
0.445 110 20 20 20 AD
12/3 Stranded 10 Solid
Aluminum
0.450 118 20 20 20 AD
12/4 Solid 10 Solid
Aluminum
0.480 134 20 20 20 AD
12/4 Stranded 10 Solid
Aluminum
0.515 145 20 20 20 AC
10/2 Solid 8 Solid Aluminum 0.485 123 30 30 30 AD
10/2 Stranded 8 Solid Aluminum 0.530 130 30 30 30 AC
10/3 Solid 8 Solid Aluminum 0.520 162 30 30 30 AB
10/3 Stranded 8 Solid Aluminum 0.565 173 30 30 30 AB
10/4 Solid 8 Solid Aluminum 0.565 162 30 30 30 AB
10/4 Stranded 8 Solid
Aluminum
0.645 216 30 30 30 AB
+ Allowable ampacities shown are for general use as specified by the National Electrical Code, 2008 Edition, Section 310.15.
60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for size #14 through 1 AWG conductors.
75°C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.
90°C - For ampacity derating purposes.
If the equipment is marked for use at higher temperature, the conductor ampacity shall be limited to the following per NEC
110.14(C)
Dimensions are nominal and subject to normal manufacturing tolerances and should be used for reference purposes only.
Standard Packaging
A - 250' Coil
B - 500' Reel
C - 750' Reel
D - 1000' Reel
MC-AP Type MC All Purpose