Cut Sheet

1-800-945-5542
© Priority Wire & Cable, Little Rock, AR PWC-2010
Tray Cable UL Type TC / TC-ER – 600V
THHN Insulation – PVC Jacket
PWC Part
Number
Size
AWG
No. of
Conductors
No. of
Strands
Insulation
Thickness
Nylon
Thickness
Jacket
Thickness
Overall
Diameter
Weight
LBS/1000'
PWC01L5 **
10 2 7 0.020” 0.004" .080" .650 x .440" 120
PWC02L5
10 3 7 0.020” 0.004" .080" .450" 160
PWC03L5
10 4 7 0.020” 0.004" .080" .515" 210
PWC04L5
10 5 7 0.020” 0.004" .080" .570" 273
PWC05L5
10 7 7 0.020” 0.004" .080" .620" 362
PWC06L5
10 9 7 0.020” 0.004" .080" .763" 467
PWC07L5
10 12 7 0.020” 0.004" .080" .810" 573
PWC08L5
10 16 7 0.020” 0.004" .080" .975" 817
PWC09L5
10 19 7 0.020” 0.004" .080" 1.020" 920
** Flat Construction
All values are nominal and subject to correction.
Application: Power, control, signal, communication and lighting circuits, For installation in cable trays in
accordance with Article 336. Cable is approved for use in raceways, supported by
messenger wire in open air, for direct burial applications, in Class I & II division 2 hazardous
locations and for Class 1 circuits as permitted in Article 725.11(b). May be installed in both wet and
dry locations or in areas exposed to chemicals and oils.
Conductors: Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8
Insulation: Heat and moisture resistant Polyvinylchloride (PVC) per UL 62.
Clear Polyamide (Nylon) jacket per UL 62.
Color Code: ICEA Method 1, E2 - E1 available upon request (Formerly K2 or K1)
Assembly: Conductors are cabled together with or without fillers as required to form a round, compact
cable core and with a binder tape.
Jacket: Sunlight resistant black PVC rated 90°C per UL 1277.
Flame Test: IEEE 383 70,000 BTU vertical tray flame test