Installation Instructions

TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
5
Communication objects
Number
Name
Object function
C
R
W
T
U
Objekt size
Data type
1 Send ‘0’ in operation output C - - T - 1 Bit Boolean
1 Send ‘1’ in operation output C - - T - 1 Bit Boolean
2 Request status input C - W - - 1 Bit switching
31 T: Temperature value [°C] output C - - T - 2 Bytes float value, Temperature (°C)
32 T: Temperature value external [°C] input C - W - - 2 Bytes float value, Temperature (°C)
33 T: Request temperature value input C - W - - 1 Bit trigger
34 T: Sensor error output C - - T - 1 Bit Boolean
35 T: Heat alarm output C - - T - 1 Bit Boolean
36 T: Frost alarm output C - - T - 1 Bit Boolean
37 RTR: Comfort temperature input C - W - - 2 Bytes float value, Temperature (°C)
38
RTR: Standby setback when heating
input
C
-
W
-
-
2 Bytes
float value, Temperature (°C)
39 RTR: Eco setback when heating input C - W - - 2 Bytes float value, Temperature (°C)
40 RTR: Standby increment when cooling input C - W - - 2 Bytes float value, Temperature (°C)
41
RTR: Eco increment when cooling
input
C
-
W
-
-
2 Bytes
float value, Temperature (°C)
42 RTR: Current set point temperature output C - - T - 2 Bytes float value, Temperature (°C)
43 RTR: Comfort temperature +/- 0,1K input C - W - - 1 Bit up/down
44 RTR: Standby setback when heating +/- 0,1K input C - W - - 1 Bit up/down
45 RTR: Eco Setback when heating +/- 0,1K input C - W - - 1 Bit up/down
46 RTR: Standby increment when cooling +/- 0,1K input C - W - - 1 Bit up/down
47 RTR: Eco increment when cooling +/- 0,1K input C - W - - 1 Bit up/down
48 RTR: HVAC mode: 1=comf, 2=stdb, 3=eco output/input C - - - - 1 Byte HVAC mode
49 RTR: Comfort mode enabled input C - W - - 1 Bit trigger
50 RTR: Standby mode enabled input C - W - - 1 Bit trigger
51 RTR: Eco mode enabled input C - W - - 1 Bit trigger
52 RTR: Status heating output C - - T - 1 Bit switching
53 RTR: Status cooling output C - - T - 1 Bit switching
54 RTR: Control value main level heating output C - - T - 1 Byte counter pulses (0...255)
54 RTR: Control value main level heating output C - - T - 1 Byte percent (0...100%)
54 RTR: Control value main level heating output C - - T - 1 Bit switching
54 RTR: Control value main level heating output C - - T - 1 Bit switching
55
RTR: Control value extra level heating
output
C
-
-
T
-
1 Byte
counter pulses (0...255)
55 RTR: Control value extra level heating output C - - T - 1 Byte percent (0...100%)
55 RTR: Control value extra level heating output C - - T - 1 Bit switching
55
RTR: Control value extra level heating
output
C
-
-
T
-
1 Bit
switching