Installation Instructions

TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
39
5.2.2.2 E1 Output
Designation
Options
Description
Filters
Inactive
Low
Medium
High
(mean of 4 measurements)
(mean of 16 measurements)
(mean of 64 measurements)
Filter disabled.
Filter active with minimum filter function.
Filter active with medium filter function.
Filter active with high filter function.
Send output value
Upon request
In case of change
Cyclically
In case of change and cyclic
Send value only upon request.
Send value upon change (see following parameters).
Send value cyclically (see following parameters).
Send value upon change and cyclically (see following two parameters).
Output value is sent from
x% change in output range
1…100%
Applies to send In case of changeand Send value upon change and cyclically“:
Parameter for necessary change before sending the value.
Output value is sent every … s
5 seconds
24 hours
Applies to send „cyclicallyandSend value upon change and cyclically“: Configuration
of interval, when value is sent.
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.
Communication object (blocking object) for input is enabled.