Installation Instructions

TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
34
5.2.1.6 Switching sequences
Designation
Options
Description
Input is being
actuated
Closed
Opened
Definition of function of input either as NO or NC contact.
Number of steps
2…5
Definition of number of total steps
Switching sequence
type
Activate/deactivate
(one button)
Activate/deactivate
(several buttons)*
All possibilities
(„Gray-Code“)
Direction
at actuation
Switch up
Switch down
Debouncing time
10 to 150 ms
Definition of debouncing time for the input.
Activate minimum
signal duration
Inactive
Active
At contact opening
in value x 0,1 s
At contact closing
in value x 0,1 s
1…65535 x 0,1 seconds
1…65535 x 0,1 seconds
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.
Communication object (blocking object) for input is enabled.
* Information - switching sequence type = „activate/deactivate (several buttons)“:
When using above mentioned option, two binary inputs are to be configured as
“switching sequences”. One of these inputs has to be configured as „direction at
actuation“ = switch up, the other input has to be configured as “switch down”. In
order to assure synchronous function of these two inputs / sequences, the two
communication objects „actuating number“ of the two inputs have to be assigned to
the same group address.
Example:
Use of E1 for switching up, E2 for switching down
E1 actuating number group address 1/1/5
E2 actuating number group address 1/1/5