Installation Instructions

TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
32
Designation
Options
Description
Differentiation
between short and
long actuation
Inactive
No differentiation between short and long actuation of input. Thereby:
Opening the contact leads to event 0.
Closing the contact leads to
event 1.
Activate minimum signal
duration
Inactive
Active
Function disabled.
Minimum signal duration for open / close configurable (see the following parameter).
At contact opening
in value x 0,1s
1…65535
x 0,1 seconds
Parameter for minimum signal duration of open contact.
At contact closing
in value x 0,1s
1…65535
x 0,1 seconds
Parameter for minimum signal duration of „close contact“.
Query input after download,
ETS reset and bus voltage
recovery
Inactive
Active
Function disabled.
Configurable waiting time before transmission after a restart. (0…30000 seconds)
Active
Differentiation between short and long actuation of input active. Thereby:
Short actuation event 0;
Long actuation
event 1
Long actuation from …s
0,3 to 10,0 seconds
If active, definition of when to count the actuation as a „long actuation“ can be done.
Input is being actuated
Closed
Opened
Definition of function of input either as NO or NC contact.
Reaction in case of
event 0 / 1
Inactive
Switch
Priority
1-Byte value
Scene
2-Byte value
2-Byte floating point
4-Byte value
If inactive function disabled.
Selection of the desired data / transmission type.
Sent value
Selection depending on
configuration of
parameter “reaction in
case of event 0/1
Debouncing time
10 to 150 ms
Definition of debouncing time for the input.
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.
Communication object (blocking object) for input is enabled.