Installation Instructions
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH
23
4.3 Temperature control – Set points
Designation
Options
Description
Comfort temperature
18° to 30°C
In 0,1 °C Steps
Definition of the comfort temperature.
Setback of standby heating
and increment of standby
cooling
0 K to 10 K
In 0,1 K Steps
Definition of the difference to the comfort temperature in Kelvin.
Setback of eco heating and
increment of eco cooling
0 K to 10 K
In 0,1 K Steps
Definition of the difference to the comfort temperature in Kelvin.
Interval to main level
heating and cooling
0 K to -10 K
In 0,1 K Steps
To get a faster compensation for big differences between the recent value and setpoint, an extra
level for heating / cooling can be activated. The distance to the main level gives the difference of
recent value and setpoint at which the extra level should be activated.
Send setpoint temperature
when changing
Disabled
Enabled
No function.
If there is a change the recent control value is sent.
Send setpoint temperature
cyclically
Disabled
Every minute – once a day
No function.
Cyclic Sending of the recent control value.
Dead zone between heating
and cooling
0 to 10K
In 0,1 K Steps
Definition of the dead zone between heating and cooling.
Recent value < Set point = Heating
Recent value > Set point + dead zone = Cooling
Min. guide value heating
-50°C to +50°C
In 0,1 °C Steps
Lower guide value for outdoor temperature reset.
Max. guide value heating
-50°C to +50°C
In 0,1 °C Steps
Upper guide value for outdoor temperature reset.
Max. increment min. guide
value heating
0 to 10K
In 0,1 K Steps
Increment of the set temperature at minimum guide value.
Min. guide value cooling
-50°C to +50°C
In 0,1 °C Steps
Lower guide value for outdoor temperature reset.
Max. guide value cooling
-50°C to +50°C
In 0,1 °C Steps
Upper guide value for outdoor temperature reset.
Max. setback for max. guide
value cooling
0 to 10K
In 0,1 K Steps
Setback of the set temperature at maximum guide value.