Installation Instructions

TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
20
3. Temperature Alarms
Designation
Options
Description
Frost alarm
Disabled
Enabled
No function.
If the alarm function is activated an alarm in the form of an object is sent when the temperature
falls below a defined temperature threshold for frost alarm.
Frost alarm
when temperature
< 1 °C to < 10 °C
When falling below the defined temperature the object frost alarm is sent.
Send frost alarm
when change of
status
Disabled
Enabled
No function.
If there is a change the recent control value is sent.
Send frost alarm
cyclically
Disabled
Every minute once a
day
No function.
Cyclic sending of the recent control value.
Heat alarm
Disabled
Enabled
No function.
If the alarm function is activated an alarm in the form of an object is sent when the temperature
exceeds a defined temperature threshold for heat alarm.
Heat alarm when
temperature
> 20 °C to > 30 °C
When exceeding the defined temperature, the object heat alarm is sent.
Send heat alarm
when change of status
Disabled
Enabled
No function.
If there is a change the recent control value is sent.
Send heat alarm
cyclically
Disabled
Every minute once a
day
No function.
Cyclic sending of the recent control value.