Installation Instructions
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH
19
2. Temperature Sensor
Designation
Options
Description
Temperature
Disabled
Temperature sensor disabled.
Sensor
Enabled
Error
Temperature sensor
Notify
Don’t notify
If there are no new values provided from the sensor for more than 10 minutes, a sensor failure will
be reported.
No report on sensor failure.
Send temperature
when changing
Disabled
Change from 0,1 K –
10,0 K
No function.
The new value is sent if the difference between old and new value is above the defined sending
threshold.
Send temperature
Disabled
No function.
cyclically
Every minute – once a
day
Cyclic sending of the recent value.
Value offset
-5 K to + 5 K
The value is adjusted by this offset. A correction might be necessary in different causes. (e.g.
sensor is placed at an unfavorable position, next to a window.
External value
Disabled
No function.
Enabled
Percentage:
With xx% proportion
Only use external value
The internal and an external value are taken pro rata to calculate an overall value. This value is
relevant for the control and the sending procedure is as defined above.
It only uses the value from the external sensor. The internal (integrated) sensor will not be used.