Installation Instructions
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH
13
Number Name Object function C R
W T U Objekt size Data type
141
E4 Output value
output
C
-
-
T
-
2 Bytes
float value, Temperature (°C)
142 E4 dimming output C - - T - 4 Bit 3-Bit controlled, Dimmer step
142 E4 STOP/slat adjustment output C - - T - 1 Bit step
142 E4 switch (Event 1) output C - - T - 1 Bit switching
142 E4 priority (Event 1) output C - - T - 2 Bit priority switching
142 E4 1-Byte value (-128...127) (Event 1) output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255)
142 E4 1-Byte value (0...255) (Event 1) output C - - T - 1 Byte counter pulses (0...255)
142 E4 Scene (Event 1) output C - - T - 1 Byte scene control
142 E4 2-Byte value (-32.768...32.767) (Event 1) output C - - T - 2 Bytes 2-Byte signed value, pulses difference
142 E4 2-Byte value (0...65.535) (Event 1) output C - - T - 2 Bytes 2-Byte unsigned value, pulse
142 E4 4-Byte value (-2.147.483.648...2.147.483.647) (Event 1) output C - - T - 4 Bytes 4-Byte signed value, counter pulses
142 E4 4-Byte value (0...4.294.967.295) (Event 1) output C - - T - 4 Bytes 4-Byte unsigned value, counter pulses
142 E4 2-Byte Floating point (Event 1) output C - - T - 2 Bytes float value, Temperature (°C)
142 E4 switching level 2 output C - - T - 1 Bit switching
142 E4 switching 2 actuation output C - - T - 1 Bit switching
142 E4 ZZ: Counter reading 1-Byte-value output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255)
142 E4 ZZ: Counter reading 1-Byte-value output C - - T - 1 Byte counter pulses (0...255)
142 E4 ZZ: Counter reading 2-Byte-value output C - - T - 2 Bytes 2-Byte signed value, pulses difference
142 E4 ZZ: Counter reading 2-Byte-value output C - - T - 2 Bytes 2-Byte unsigned value, pulse
142 E4 ZZ: Counter reading 4-Byte-value output C - - T - 4 Bytes 4-Byte signed value, counter pulses
142
E4 Output value request
input
C
-
W
-
-
1 Bit
switching
142 E4 Output value request input C - W - - 1 Bit switching
143 E4 Start event 0/1 input C - W - - 1 Bit switching
143
E4 End position top
input
C
-
W
-
-
1 Bit
Boolean
143 E4 Scene storage display output C - - T - 1 Bit enable
143 E4 switching level 3 output C - - T - 1 Bit switching
143 E4 switching 3 actuation output C - - T - 1 Bit switching
143 E4 HZ: Counter reading request input C - W - - 1 Bit switching
143 E4 Measured value out of range output C - - T - 1 Bit switching
143 E4 Measured value out of range output C - - T - 1 Bit switching
144 E4 End position bottom input C - W - - 1 Bit Boolean
144 E4 switching level 4 output C - - T - 1 Bit switching
144 E4 switching 4 actuation output C - - T - 1 Bit switching
144 E4 HZ: Limit value exceeded output C - - T - 1 Bit Boolean
144 E4 Heating temperature limit output C - - T - 1 Bit switching