Installation Instructions

TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
10
Number Name Object function C R
W T U Objekt size Data type
103
E2 Switching level 3
output
C
-
-
T
-
1 Bit
switching
103 E2 Switching 3 actuation output C - - T - 1 Bit switching
103 E2 HZ: Counter reading request input C - W - - 1 Bit switching
104 E2 End position bottom input C - W - - 1 Bit Boolean
104 E2 Switching level 4 output C - - T - 1 Bit switching
104 E2 Switching 4 actuation output C - - T - 1 Bit switching
104 E2 HZ: Limit value exceeded output C - - T - 1 Bit Boolean
105 E2 Store scene input C - W - - 1 Bit enable
105 E2 Enable save input C - W - - 1 Bit enable
105 E2 switching level 5 output C - - T - 1 Bit switching
105 E2 Switching long actuation output C - - T - 1 Bit switching
106 E2 Level up/down switching input C - W - - 1 Bit switching
106 E2 ZZ: Limit value exceeded output C - - T - 1 Bit Boolean
107 E2 Number actuations input C - W - - 1 Byte counter pulses (0...255)
107 E2 ZZ: Counter reading request input C - W - - 1 Bit switching
108 E2 ZZ: Reverse direction input C - W - - 1 Bit Boolean
109 E2 ZZ: reset input C - W - - 1 Bit Boolean
110 E2 ZZ: Stop input C - W - - 1 Bit Boolean
119 E2 Disable input C - W - - 1 Bit enable
121 E3 switching sensor output C - - T - 1 Bit switching
121
E3 Alarm sensor
output
C
-
-
T
-
1 Bit
1-Bit, Alarm
121 E3 switching output C - - T - 1 Bit switching
121 E3 Blinds UP/DOWN output C - - T - 1 Bit up/down
121
E3 Switch (event 0)
output
C
-
-
T
-
1 Bit
switching
121 E3 Priority (event 0) output C - - T - 2 Bit priority switching
121 E3 1-Byte value (-128...127) (Event 0) output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255)
121 E3 1-Byte value (0...255) (Event 0) output C - - T - 1 Byte counter pulses (0...255)
121 E3 Scene (Event 0) output C - - T - 1 Byte scene control
121 E3 2-Byte value (-32.768...32.767) (Event 0) output C - - T - 2 Bytes 2-Byte signed value, pulses difference
121 E3 2-Byte value (0...65.535) (Event 0) output C - - T - 2 Bytes 2-Byte unsigned value, pulse
121 E3 4-Byte value (-2.147.483.648...2.147.483.647) (Event 0) output C - - T - 4 Bytes 4-Byte signed value, counter pulses
121 E3 4-Byte value (0...4.294.967.295) (Event 0) output C - - T - 4 Bytes 4-Byte unsigned value, counter pulses
121 E3 2-Byte Floating point (Event 0) output C - - T - 2 Bytes float value, Temperature (°C)
121 E3 Scene output C - - T - 1 Byte scene control
121 E3 switching level 1 output C - - T - 1 Bit switching