TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Technical manual TS 3x.10 knx Application description – room temperature sensor & control General Information The device fits for the particular use of the following tasks: monitoring of the air quality in building systems technology (schools, offices, hotels, conference venue etc.), data transfer and regulation via bus system. The device is intended for use in accordance with the defined technical data.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Table of contents General Information ......................................................................................................................................................................................................................................................................................... 1 Application program .................................................................................................................................
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Application program Manufacturer: Program name: Installation: Hugo Müller GmbH & Co KG, Sturmbühlstraße 145-149, D-78054 VS-Schwenningen TS 3x.10 knx Add the device to your device list and open a new project. You can download the ETS database on our webpage: http://www.hugo-mueller.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Overview parameters Parameters Subcategory parameters Description Global settings Global settings Send „in operation “(incl. cycle time), request status (active/inactive, request with…), send delay after bus voltage recovers in seconds. Temperature Temperature sensor Settings temperature sensor: Enable – disable, send measured values, offset adjustment, notification of sensor error, external value enabled/disabled.
TECHNICAL MANUAL TS 3x.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 56 RTR: Control value main level cooling Object function output C - - T - 1 Byte counter pulses (0...255) 56 RTR: Control value main level cooling output C - - T - 1 Byte percent (0...
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 81 E1 1-Byte value (-128...127) Object function output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 81 E1 1-Byte value (0...255) output C - - T - 1 Byte counter pulses (0...255) 81 E1 2-Byte value (-32.768...32.767) output C - - T - 2 Bytes 2-Byte signed value, pulses difference 81 E1 2-Byte value (0...65.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 84 E1 switching 4 actuation Object function output C - - T - 1 Bit switching 84 E1 HZ: Maximum level exceeded output C - - T - 1 Bit Boolean 84 E1 threshold output C - - T - 1 Bit switching 84 E1 threshold output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 101 E2 2-Byte value (-32.768...32.767) (Event 0) Object function output C - - T - 2 Bytes 2-Byte signed value, pulses difference 101 E2 2-Byte value (0...65.535) (Event 0) output C - - T - 2 Bytes 2-Byte unsigned value, pulse 101 E2 4-Byte value (-2.147.483.648...2.147.483.647) (Event 0) output C - - T - 4 Bytes 4-Byte signed value, counter pulses 101 E2 4-Byte value (0...4.294.967.
TECHNICAL MANUAL TS 3x.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 121 E3 switching 1 actuation Object function output C R W T U C - - T - 1 Bit switching 121 E3 HZ: Counter reading 1-Byte-value output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 121 E3 HZ: Counter reading 1-Byte-value output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL TS 3x.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 141 E4 Output value Object function output C R W T U C - - T - 2 Bytes float value, Temperature (°C) 142 E4 dimming output C - - T - 4 Bit 3-Bit controlled, Dimmer step 142 E4 STOP/slat adjustment output C - - T - 1 Bit step 142 E4 switch (Event 1) output C - - T - 1 Bit switching 142 E4 priority (Event 1) output C - - T - 2 Bit priority switching 142 E4 1-Byte value (-128...
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 145 E4 Store scene Object function input C R W T U C - W - - 1 Bit enable 145 E4 Enable save input C - W - - 1 Bit enable 145 E4 switching level 5 output C - - T - 1 Bit switching 145 E4 Switching long actuation output C - - T - 1 Bit switching 145 E4 Bit threshold 1 output C - - T - 1 Bit switching 145 E4 Byte threshold 1 output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Object function input C R W T U Objekt size Data type C - W - - 1 Bit enable C - - 1 Bit switching - 1 Bit 1-Bit, Alarm - 1 Bit switching - 1 Bit up/down T - 1 Bit switching T - 2 Bit priority switching - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Number Name Objekt size Data type 162 E5 switching level 2 Object function output C R W T U C - - T - 1 Bit switching 162 E5 switching 2 actuation output C - - T - 1 Bit switching 162 E5 ZZ: Counter reading 1-Byte-value output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255) 162 E5 ZZ: Counter reading 1-Byte-value output C - - T - 1 Byte counter pulses (0...
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Communication flags Flag C R W T U Name Communication Read Write Transmit Update Meaning Object can communicate Object status can be requested (ETS, display etc.) Object can receive information Object can send information Object can request a value from another bus participant. The answer is interpreted as write command and updates the value of the communication object. This is typically used to request external sensor data after a bus voltage recovery.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 1. Global Settings (Picture shows modified parameters) Designation Send in operation Request status Send delay after bus voltage recovery …s Options Inactive Sends „0“ Sends „1“ Inactive Active Description No function. „In operation“ (0 or 1) will be send in the configured cycle time (see next parameter).
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 2. Temperature Sensor Designation Temperature Sensor Options Disabled Enabled Description Temperature sensor disabled.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 3. Temperature Alarms Designation Frost alarm Options Disabled Enabled Frost alarm when temperature Send frost alarm when change of status Send frost alarm cyclically Heat alarm Disabled Enabled Heat alarm when temperature Send heat alarm when change of status Send heat alarm cyclically < 1 °C to < 10 °C Description No function.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 4. Temperature control 4.1 Temperature control – heating and cooling PI control: A PI control is a constant control that comprises a proportional part (P-part) and an integral share (I-share). The size of the P-part is indicated in Kelvin, the I-share in minutes. At a constant PI control, the manipulated variables are operated in proportional steps up to a maximum value.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 4.2 Temperature control – General Designation Blocking object heating mode: enable Options Disabled Description Blocking object disabled. Enabled Blocking object cooling mode: enable Disabled If the blocking object is activated, the reception of an external object can prevent the sending of the manipulated variable. Thereby an undesirable starting of actors can be prevented (e.g. do not heat if a window is open). Blocking object disabled.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 4.3 Temperature control – Set points Designation Comfort temperature Setback of standby heating and increment of standby cooling Setback of eco heating and increment of eco cooling Interval to main level heating and cooling Options 18° to 30°C 0 K to 10 K In 0,1 °C Steps In 0,1 K Steps Description Definition of the comfort temperature. Definition of the difference to the comfort temperature in Kelvin.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 4.4 Temperature control – Main level and extra level heating / cooling (Picture shows main level heating, PI control with output: PWM) Designation Control type Options PI control Proportional band Reset time Control value output format PWM cycle Min.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5. Inputs 5.1 General Designation Limit number of telegrams Options Inactive Active Maximum number of sent telegrams Maximum number of sent telegrams per Description No function. Number of telegrams to be sent is limited to the configured maximum. 1 to 255 Maximum number of telegrams to be sent. 50 milliseconds to 60 seconds Base for number of telegrams.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2 E1 – E5 General Designation Designation Function Options Inactive Binary input (available for E1-E5) Analogue input (E1 only) External temperature sensor (E4 only) Switching / Alarm Dimming Blind Value Scene Switching sequences Multiple operation Pulse counter Description Possibility to name each input individually. Input disabled. Available for inputs E1 to E5 (in total up to 5x). Definition of the desired use each specific input.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1 5.2.1.1 E1 – E5 as binary inputs Switching/Alarm function (Picture shows input 1, with function as binary input. Configuration windows for inputs E2…E5 are similar). Description of functions and parameters see next page.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH Designation Switching / alarm sensor Differentiation between short and long actuation Options Switch Alarm Inactive Active Enable object „start event 0/1“ Inactive Active Reaction in case of event 0 Reaction in case of event 1 Cyclical sending Inactive Active Debouncing time… in ms Enable object Inactive „disable“ Active Description Communication object type DPT 1.001 Communication object type DPT 1.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.2 Dimming Designation Switching/ Dimming sensor Options Dimmer / switch Description Selection of operating mode as dimmer / switch. Long actuation from … in s At short actuation (switching): At long actuation (dimming direction): Dimmer Dimming procedure Debouncing time Enable object „disable“ Start / Stop Steps Inactive Active 0,3 to 10,0 seconds Configuration of time before input signal is registered as a “long actuation”.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.4 Value / forced operation Description of parameters see next page.
TECHNICAL MANUAL TS 3x.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.5 Scene Designation Input is being actuated Scene number at actuation Save scene Options Closed Opened 1…64 No At long actuation Description Definition of function of input either as NO or NC contact. Selection of the scene number to be transmittet on actuation of input. Long actuation from …s With object value= 1 At long actuation and object value= 1 Debouncing time Enable object „disable“ 10 to 150 ms Inactive Active Scenes cannot be saved.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.6 Switching sequences * Information - switching sequence type = „activate/deactivate (several buttons)“: When using above mentioned option, two binary inputs are to be configured as “switching sequences”. One of these inputs has to be configured as „direction at actuation“ = switch up, the other input has to be configured as “switch down”.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.7 Multiple operation Designation Input is being actuated Max. number of actuations Sent value Update and send at actuation Maximum time between two actuations … in s Additional object for long actuation Debouncing time Enable object „disable“ Options Closed Opened 1…4 On Off Switchover Inactive Description Definition of function of input either as NO or NC contact.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.8 Pulse counter Designation Data type (main counter) Limit value 1 Limit value 2 Counting type Number of input pulses for a counting pulse Counter reading change per counting pulse Send counter reading at download, ETS reset and bus voltage recovery Send counter reading at change Send counter reading cyclically Save counter reading Options 1-Byte value 2-Byte value 4-Byte value Range depending on selected data type. Range depending on selected data type.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.1.8.1. Intermediate counter (with function pulse counter) Designation Data type (intermediate counter) Options 1-Byte value 2-Byte value 4-Byte value Range depending on selected data type. Limit value 1 Range depending on selected data type.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.2 Function analogue input (Only available at input E1) 5.2.2.1 E1 Voltage Designation Sensor type Lower measuring limit in % of effective range Upper measuring limit in % of effective range Output value Output value tob e sent at lower measuring limit Output value tob e sent at upper measuring limit Options 0-10 V 1-10 V 0…100% 0…100% 1-Byte 2-Byte 4-Byte Range depending on selected data type. Range depending on selected data type.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.2.2 E1 Output Designation Filters Send output value Enable object „disable“ Options Inactive Low (mean of 4 measurements) Medium (mean of 16 measurements) High (mean of 64 measurements) Upon request In case of change Cyclically In case of change and cyclic Output value is sent from 1…100% x% change in output range Output value is sent every … s 5 seconds … 24 hours Inactive Active Description Filter disabled. Filter active with minimum filter function.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.2.3 E1 Threshold value Designation Use threshold value Options Inactive Active Tolerance band lower limit in % of output range Tolerance band upper limit in % of output range Limit value changeable via bus Data type of threshold value object Send if threshold value undershot Send if threshold value exceeded Minimum duration of overshoot Minimum duration of overshoot 0…100% Description Function disabled. Function enabled.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.2.4 E1 Output threshold value Designation Send threshold value Options In case of change In case of change and cyclic Description Send threshold only in case of change. Send if threshold value undershot, every… Send if threshold value exceeded, every… 5 seconds … 24 hours Send threshold in case of change as well as cyclically (adjustable cycle).
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.3 Function external Temperature sensor (input E4/5 only) Please Note: When using input E4 as temperature sensor, E5 cannot be used as separate input. 5.2.3.1 E4 General Designation E4/5 Temperature function Options Temperature Floor heating thermal limiter Description Connection of an external temperature sensor. Connection of an external floor heating thermal limiter (sensor).
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.3.2 E4/5 External temperature sensor / floor heating thermal limiter Designation Temperature sensor type Temperature offset in K Line fault compensation Options PT1000 TF06 -5,0…+5,0 K None Length Description Selection of the connected temperature sensor type. Adjustable offset for the temperature sensor value. Function disabled.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.3.3 E4/5 Output Designation Filters Send output value Enable object „disable“ Options Inactive Low (mean of 4 measurements) Medium (mean of 16 measurements) High (mean of 64 measurements) Upon request In case of change Cyclically In case of change and cyclic Output value sent from 1…200 a change of x 0,1°C Output value is sent every 5 seconds… 24 hours Inactive Active Description Filter disabled. Filter active with minimum filter function.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.3.
TECHNICAL MANUAL TS 3x.10 KNX – ENGLISH 5.2.3.5 E4/5 Output threshold value 1 / 2 (only if E4 general temperature function = Temperature) Designation Send threshold value object 5.2.3.6 Options In case of change In case of change and cyclic Description Send threshold only in case of change. Send if threshold value undershot, every 5 seconds … 24 hours Send if threshold value exceeded, every 5 seconds … 24 hours Send threshold in case of change as well as cyclically (adjustable cycle time).