Data Sheet

climate
Highlights
n
Sensor for temperature measurement
n
Temperature sensor
(Measuring range 0 - 50 °C)
n
Clearly structured ETS
n
Up to 5 binary and analogue inputs
n
TS 31.10 knx: manual adjustment of set-point
temperature (adjustment range ±3°; increment 0.5°).
Display with LEDs.
n
Sensor for room temperature control
n
Easy handling and mounting
n
Modern and planar design
n
Up to 5 binary and analogue inputs
n
TS 31.10 knx: Set-point temperature manually
adjustable (Adjustment range ±3°)
Following data and functions will be provided to the KNX bus and
can be configured within ETS software:
knx
Con ne ct
Room temperature controls TS 3x.10 knx
for wall mounting
Rights to technical amendments reserved.
n
Room temperature control
Up to 5 binary and analog inputs
n
Sensors
Order number
Housing colour
TS 30.10 knx
Temperature
TS 31.10 knx
Temperature
Version
for wall mounting
for wall mounting
Man. temp. adjustment
± 3° manually via Keypad
Technical data
Power supply
via KNX bus voltage
0°...+50°C
self-extinguishing thermoplastic
PCB Push-in terminal block
IP 20 (DIN EN 60529)
Permitted ambient temperature
Housing
Type of connection (KNX)
Type of protection
Bus current
approx. 10 mA
III when installed according to regulations
Class of protection
wall mounting, preferrably combined with hollow-wall box
Mounting
Housing color
studio white (similar to RAL 9016)
Bus system
KNX
Sensors
Temperature
Measuring range temperature
0-50 °C
Manual operation
(TS31.10 knx only)
manual adjustment of set-point temperature
(adjustment range ±3°; increment 0.5°)
The ETS-Software (> V4.2) of the room temperature controls TS 3x.10 knx offers:
Temperature:
and much more...
Value output
Control heating / cooling (2-point and PI control)
Alarms
TS 30.10 knx
TS 31.10 knx
TS 31.10 knx
TS 30.10 knx
80,50
80,50
17
Additional information / accessories
Accessory: External temperature sensor TF06 Müller
with 4m cable to connect to analogue input
of TS 31.10 knx or TS30.10 knx
(not included in delivery / sold separately)
Technical data TF06 Müller:
measuring range -15..+70°C
sensor type: NTC 10 kilo-ohms
sensor length: 28 mm, diameter: 7,7 mm
cable: 4m PVC/PVC black (H03 VV-F)
External inputs (binary / analogue):
Pin
Function
1
Binary input
2 Binary input
3 Binary input
4 Binary input
5 Binary input
6 GND
Terminal
1 2 3 4 5 6
J
J
0-10
V
Option 2
Pin assignment option 1*:
Pin
Function
1
0-10V / 1-10V
2 Binary input
3 Binary input
4 Ext. temperature-
5 sensor (PT1000)
6 GND
Pin assignment option 2*:
Terminal
Option 1
1 2 3 4 5 6
* Selection of input functions / options
via ETS - parameter configuration
Wire diameter max. 6x 0,5 mm², strip length 7 mm
Type of connection external inputs