Operation Manual

BA LS30knx HARDWARE N; DE,GB -23338-ED-V01
KNX light and
temperature sensor
Safety issues
Usage
!!ATTENTION!! DANGER OF LIFE / RISK OF FIRE AND ELECTRIC
SHOCK!!
=> Installation and assembly of electrical equipment must be carried out only
by professional electrician!
=> Disconnect device from power supply for wiring and installation purposes!
=> Defective devices have to be put out of service immediately!!!
Connect only to suitable supply voltage/frequency. Only operate the KNX
light sensor with extra-low voltage!
Warranty void if housing opened by unauthorised person!
The electronic circuit is protected against a wide range of external influences.
Incorrect operating may occur if external influences exceed certain limits!
Installation and assembly of electrical equipment must be in accordance with
national building, electrical and safety codes!
Observe the regulations and instructions in the ZVEI/ZVEH handbook
(building system technology). Especially the professional installation of the
bus lines and the professional installation and start-up of KNX devices must
be observed!
Usage:
TheKNX light and temperature sensor can send the
following data to the KNX bus: Outside temperature / Lux
values
Following data and functions will be offered for the KNX bus
(via ETS): Temperature control, light control, twilight switch
with daily program, daily time switch
Technical data
Power Supply:
via KNX bus voltage (nominal voltage 29V)
Bus current:
approx. 10 mA
Bus system:
KNX
Type of protection:
IP 54 (DIN EN 60529)
Permitted ambient temperature:
-30°C 5C
Specifications // Compliance:
EN 60730 // CE
Housing:
self-extinguishing thermoplast
Assembly:
wall mounting with mounting bracket
Type of connection:
KNX bus terminal
Rights to technical amendments reserved
Installation instruction
Make sure that there are no transformers, relays, switches, or similar devices within a radius of one meter around the KNX light and temperature sensor.
If mounted on wall, avoid electric cables and other disturbing metal in the wall.
Installation and connection of the device
Connection / wall mounting
Remove both screws on the bottom side and remove the bottom cover.
Guide wire through the cable sleeve and the hole of the bottom cover.
Connect the wire to the removable BUS terminal block (Please note polarity).
Plug BUS terminal block to pins on PCB
Program the KNX light and temperature sensor (please see pointConfiguration).
Assemble cable sleeve on the bottom cover.
Screw the bottom cover.
Install wall mounting bracket and attach the KNX light and temperature sensor (see drilling plan).
Configuration
The parameterization will be assigned by the ETS-software: Physical address, group address, parameter settings
Programming the KNX light and temperature sensor
Press the learning key
RESULT => The KNX-LED lights up (until the ETS-software programs the KNX light and temperature sensor)
PLEASE NOTE => You can confirm the correct programming with the ETS-software
Take care of the environment!
Recycle properly!
Drilling plan for wall mounting bracket [ NOT TRUE TO SCALE ]