Installation Instructions
BA LS30knx Anwendungsprogramm HM; DE,GB - 23346 - ED – V01
INSTRUCTION MANUAL ENGLISH – PAGE 1 / 2
ENGLISH
Application program
„LS 30.00 knx“
Usage: KNX light and temperature sensor LS 30.00 knx
Usage:
The “KNX light and temperature sensor” can send the following data to the KNX bus: Outside temperature /
Lux values. Following data and functions will be offered for the KNX bus (via ETS):
Temperature control, light
control, twilight switch with daily program, daily time switch
Technical data: KNX light and temperature sensor LS 30.00 knx
Power Supply:
via KNX bus voltage (nominal voltage 29V)
Bus current:
approx. 10 mA
Bus system:
KNX
Type of protection:
IP 54 (DIN EN 60529)
Permitted ambient temp.:
-30°C … 55°C
Specifications // Compliance:
EN 60730 // CE
Housing:
self-extinguishing thermoplastic
Assembly:
wall mounting with mounting bracket
Type of connection:
KNX bus terminal
Rights to technical amendments reserved
Application program
Manufacturer:
Hugo Müller GmbH & Co KG
Program name:
LS 30.00 knx
Communication objects
Number
Name
Object Function
Data Type
19
Send temperature to bus
Send
9.001 temperature (°C)
20
Send light value (lux) to bus
Send
9.004 lux (lux)
21
Bus request to send temperature
Receive
1.017 1-bit
22
Bus request to send light value (lux)
Receive
1.017 1-bit
24
Send light above/below threshold 1
Send
1.001 1-bit
25
Send light above/below threshold 2
Send
1.001 1-bit
26
Send temperature above/below setpoint
Send
1.001 1-bit
27
Send scene light above/below threshold 1
Send
17.001 scene number
28
Send scene light above/below threshold 2
Send
17.001 scene number
29
Send scene temperature above/below setpoint
Send
17.001 scene number
33
Send standard time switch
Send
1.001 1-bit
34
Receive date from bus
Receive
11.001 date
35
Receive time from bus
Receive
10.001 time of day
36
Receive temperature from bus
Receive
9.001 temperature (°C)
37
Receive light value (lux) from bus
Receive
9.004 lux (lux)
40*
Blocking object light control threshold 1
Receive
1.003 enable
41*
Blocking object light control threshold 2
Receive
1.003 enable
42*
Blocking object temperature control
Receive
1.003 enable
* Functions available in ETS application program LS 30.00 knx Version 4.0, only in combination with hardware manufactured in CW16/2017 or later.